Remove Jumper if
Emergency Stop is
Used.
Emergency
Emergency
Stop
Stop
B+
1
1A
56
42A 2
P2
CIRCUIT BOARD TERMINAL IDENTIFICATION (TB1)
1 -
Ground— Emergency Stop Relay (K4)— Connect Emergency Stop Across Terminals TB1-1 and 1A.
1A -
Emergency Stop Relay (K4) Coil; Negative— Connect Emergency Stop Across Terminals TB1-1 and 1A.
56 -
Not Used
-
Not Used
42A - Battery Voltage (Fuse #1 Protected)— Accessory Power Supply; Customer may also Provide Separate Accessory Power Source
2 -
Ground Terminal
9 -
Crank Mode Selection (open— cyclic crank; ground— continuous crank) Connect TB1-2 to TB1-9 for Continuous
Cranking; Leave TB1-9 open for cyclic cranking. See Starting Procedure.
48 -
Emergency Stop Indicator *
3 -
Remote Start Ground— Connect Remote Start Switch to TB1-3 and TB1-4
4 -
Remote Start— Connect Remote Start Switch to TB1-3 and TB1-4
26 -
Auxiliary Indicator (Aux.) *
12 -
Overcrank Indicator (OC) *
39 -
Overspeed Indicator (OS) *
38 -
Low Oil Pressure Indicator (LOP) *
36 -
High Engine Temperature Indicator (HET) *
60 -
System Ready Indicator *
80 -
Not In Auto Indicator *
40 -
Prealarm High Engine Temperature Indicator (PHET) *
41 -
Prealarm Low Oil Pressure Indicator (PLOP) *
32 -
Common Fault/Prealarm Line— A/V Alarm or Common Fault Relay Activated by HET, LOP, LWT, OC, OS, and AUX Faults
63 -
Low Fuel— Connect Fuel Level Sensor to TB1-63 to Activate Fault Lamp (If Used)
61 -
Battery Charger Fault— Connect Battery Charger to TB1-61 to Activate Fault Lamp (If Used)
62 -
Low Battery Volts— Connect Battery Charger to TB1-62 to Activate Fault Lamp (If Used)
35 -
Low Water Temperature— Connect LWT Sensor (Prealarm Kit) to TB1-35 to Activate LWT or LWT/AUX Lamp
NOTE: Not all terminal connections are used for all generator sets (see Wiring Diagrams).
* Indicators may be customer supplied lamps and/or alarms or A/V Alarms, Annunciators, Dry Contact Kits, etc.
TP-5631 7/96
HET
LOP
OS
OC
AUX
Remote
Switch
B--
9
48
3
4 26 12 39 38 36 60 80 40 41 32 63 61 62 35
P1
Figure 2-2. Controller TB1 Terminal Strip Connection
System Ready
Not In Auto
PHET
PLOP
Common Fault **
Low Fuel
Low Battery
LWT
** Common Fault Indicator
Activated By:
HET Fault
LOP Fault
LWT Fault
OC Fault
OS Fault
AUX Fault
Connect A/V Alarm or
Common Fault Relay Kit
Battery Charging Fault
TB1 Terminal Strip
Operation 2-5