Ac Load Lead Connections - Kohler 6.5RMY Operation Manual

Industrial generator sets
Hide thumbs Also See for 6.5RMY:
Table of Contents

Advertisement

Make the AC output lead connections in the
compartment where the AC circuit breakers are located.
Route the building distribution panel or transfer switch
leads through the bottom of generator set or flexible
conduit directly attached to the AC circuit breaker box.
Verify that leads and conduit do not interfere with the
operation of the generator set or obstruct the service
areas. Verify that the electrical installation complies
with the National Electrical Code (NEC) and is done by a
licensed electrician. All applicable local and state codes
must be followed. See Wiring Diagram manual for more
information
regarding
connections.
Top View Generator Set
1. Equipment ground
6-4 Installation

AC Load Lead Connections

generator
set
electrical
Figure 6-4. Load Lead Connections
1. Connect L1/L2 black leads to AC circuit breaker
load side.
2. Connect L0 white lead to neutral stud.
3. Connect green lead to equipment ground.
Canadian installations only:
For standby service connect output of generator set to a
suitably rated transfer switch in accordance with
Canadian Electrical Code, Part 1.