Table Of Fault Messages - Viessmann Vitoflex 300-UF Series Installation And Operating Instructions Manual

Wood-fired boiler
Hide thumbs Also See for Vitoflex 300-UF Series:
Table of Contents

Advertisement

Vitoflex 300-UF Installation & Operating

Table of Fault Messages

Fault message
Fault, high limit safety cut-out
Fault, combustion chamber,
pressure
Fault, repeat heat-up
Fault, boiler sensor faulty
Fault, boiler return sensor faulty
Fault, feed sensor faulty
Fault, flue gas temperature sensor
Fault, material shortage
Fault, water level in extinguishing
water tank
Fault, motor protection, conveyor
devices
Fault, maintenance cover open
Fault, light barrier, firebed
monitoring
O
measurement fault
2
Warning, combustion chamber
door open
Cause
Incorrect set supply temperature (too
high)
Faulty system component (boiler circuit
pump or return valve)
Amount of heat drawn drops suddenly
Flue gas fan failure
Vacuum pressure measurement failed
Heat exchanger heavily soiled
No combustion detected
Insufficient fuel or fuel too wet
Temperature sensor or lead faulty
Temperature sensor or lead faulty
Temperature sensor or lead faulty
Temperature sensor or lead faulty
Fuel store empty
Material blockage
Shut-off gate valve jammed
Too little water in the extinguishing
water tank
Motor overloaded due to blockage
(foreign body)
Bearing damage
Maintenance cover open
Sight glasses dirty
Ash deposits in apertures
Light barrier dirty or faulty
Lambda probe heavily soiled or faulty,
or O
transducer faulty
2
Combustion chamber door open or not
fully closed
Remedy
Check set supply temperature.
Check boiler circuit pump and return
temperature raising facility.
Check the heat drawn. If boiler water
temperature is below 158°F (70°C):
remove protective cap on HLSC and
press reset button.
Check flue gas fan.
Check vacuum pressure measurement.
Clean heat exchanger.
Add fuel. If fuel is above W40:
preheat the combustion chamber.
Or use suitable dry fuel.
Consult a qualified electrician.
Consult a qualified electrician.
Consult a qualified electrician.
Consult a qualified electrician.
Fill fuel store.
Switch OFF mains isolator and
remove material blockage.
Check shut-off gate valve for ease
of operation.
Fill the extinguishing water tank.
Remove foreign body.
Check bearings for ease of operation.
Close maintenance cover.
Remove and clean both sight glasses.
Remove dust and ash deposits from
the apertures.
Clean or replace the light barrier
sensors.
Contact Viessmann Technical Service.
Close combustion chamber door.
Faults
63