Viessmann Vitoflex 300-UF Series Installation And Operating Instructions Manual page 46

Wood-fired boiler
Hide thumbs Also See for Vitoflex 300-UF Series:
Table of Contents

Advertisement

Parameter
Fuel
(continued)
Parameter
"Conveyor device 1"
"Delay ON"
"Pulse"
"Pause"
"Transverse screw conveyor"
"Delay ON"
"Delay OFF"
"Runtime, transverse screw
conveyor, maximum"
"Container" or "Hydraulics"
"Delay ON"
"Emergency mode"
Selection field Auto, etc.
"Delay, empty message"
46
Description
Start delay
Setting in seconds
Period of time for which the component is on/off:
Pulse = Component is on.
Pause = Component is off.
Tip: Pause = 0 means continuous operation.
Setting in seconds
Start delay
Setting in seconds
Shutdown delay
Setting in seconds
If the maximum runtime of the transverse screw conveyor
has been exceeded, the container or pushrod discharge
will operate with the pause and pulse times specified
under "Emergency mode".
Setting in seconds
Start delay
Setting in seconds
If the runtime monitoring function for the
transverse screw conveyor is triggered, it is
assumed that bridging has occurred in the
trough. The discharge will then run using the
times specified here until the container is
empty.
See above for a definition of pulse/pause.
Auto (Automatic): If there is more than one container, the system changes over
to the next container if a fault occurs or if the container is empty.
Manual 1, 2 or 3: Container 1, 2 or 3 is in manual mode. The container in
question is ignored in the changeover.
Delay for empty message
In the event of an empty message, the system changes
over to the next available container. If no further containers
are available, a controlled system shutdown is performed.
Setting in seconds
Vitoflex 300-UF Installation & Operating
"Charging" tab
"Pulse"
"Pause"
Setting range Standard
value:
0 to 100
2
1 to 10
1
0 to 10
0
0 to 100
2
0 to 20
2.5
10 to 1000
80
0 to 200
2
0 to 200
5
0 to 600
10
10 to 800
300

Hide quick links: