Mechanical Room

Ensure the mechanical room complies with the requirements
in these instructions and local codes.
Viessmann recommends the installation of an additional
electrical disconnect switch and a fuel shut-off valve (if
possible) outside the mechanical room or enclosed area
of installation.
A separate, dry heating room must always be provided for
the Vitoflex 300-UF Grate Firing System. No combustible
materials may be stored in the heating room. The heating
boiler may only be set up on a fire and temperature-
resistant floor.
No temperature-sensitive pipes or lines may be installed
in the floor beneath the heating boiler.
The temperature in the heating room must not exceed
104°F (40°C) while the system is in operation
(in the area approx. 3 ft. (1 m) away from the boiler).
The temperature in the heating room must not fall below
50°F (10°C) while the system is in operation (measured
at the inner side of exterior walls).
Foundation dimensions
Boiler Model
a
in. (mm)
b
in. (mm)
c
in. (mm)
d
in. (mm)
e
in. (mm)
UF 390
UF 530
40e (1026)
40e (1026)
71
/
(1826)
71
/
7
7
8
8
166d (4221)
166d (4721)
49f (1260)
49f (1260)
100
/
(2561)
120b (3061)
7
8
The load-bearing capacity of the heating room floor must
be designed for the weight of the system plus filling with
water and fuel. The load-bearing capacity of the floor in
the area of the boiler bearing surface must be 512 lb/ft²
(2500 kg/m²).
IMPORTANT
Always follow the most up-to-date local, municipal and
building regulations and codes.
The minimum distance to the walls and ceiling required
according to the table of dimensions for proper cleaning
and maintenance of the boiler must be complied with.
A sufficient supply of fresh air must be provided directly
from outdoors into the heating room. Induced ventilation is
necessary for heating rooms that are confined or enclosed.
Dimensions shown in. (mm)
Hatched surface
Medium grey surface
UF 720
43c (1112)
(1826)
75a (1912)
193e (4912)
55
/
(1400)
1
8
122b (3112)
Heat-resistant floor
Boiler supporting surface
UF 950
UF 1250
53b (1360)
53b (1360)
85 (2160)
85 (2160)
222
/
200f (5096)
1
8
64
/
(6030)
64d (1630)
1
8
120c (3066)
142d (3611)
Safety
(5641)
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents