8 0 | Bosch Climate 5000 Series Ductless Air Conditioner / Heat Pump Outdoor Unit
4.
Disconnect the connector for fan motor from the electronic control board.
Figure 100
5.
Remove the four xing screws of the fan motor. Then remove the fan motor.
Figure 101
Data subject to change
9.3.3 Removing the electrical parts
1.
After removing the panel plate and fan assembly, remove the connectors for
the compressor and reactor.
Compressor
connector
Figure 102
2.
Pull out the two blue wires connected with the reversing valve.
Figure 103
3.
Pull out connectors of the condenser coil temp. sensor (T3), outdoor
ambient temp. sensor (T4) and discharge temp. sensor (T5).
Figure 104