Low Voltage Dc-Dc Lvdts; Figure 12-7: "Low Voltage" Dc-Dc Lvdt Connection To High-Level Input Channel - Honeywell SC Series Installation Instructions Manual

Signal conditioning self-calibrating digital indicators
Table of Contents

Advertisement

SC 2000, SC2001, SC3004

12.2.8 Low Voltage dc-dc LVDTs

Use the following wiring diagram when connecting a low-voltage
dc-dc LVDT to a High-Level Input channel. Examples of such
devices include
Models DLB, DLE and DLF dc-dc LVDTs
The High-Level Input channel's Configuration Jumpers must be
set as follows for proper operation. See "Excitation and Signal
Jumpers" on page 56.
(+)Excitation supply: "+12 Vdc"
(-)Excitation supply: "GND"
Signal type: "voltage"
Signal reference: "single ended"

Figure 12-7: "Low Voltage" dc-dc LVDT Connection to High-Level Input Channel

LOW-VOLTAGE
DC-DC LVDT
UNREGULATED
SUPPLY COMMON
(+)OUTPUT
OUTPUT RETURN
+5V REG. INPUT
+5V REG. OUTPUT
CABLE
008-0608-00
Rev. G,
INSTRUMENT CONNECTIONS
DESIGNATION
+12V
(+)EXCITATION
SHUNT CAL 1
SHUNT CAL 2
0V
(-)EXCITATION
(+)SIGNAL
(-)SIGNAL
(+)ANALOG OUTPUT
(-)ANALOG OUTPUT
N/C
DGND
AUX1
AUX2
NOTE KEYED CONNECTOR
CABLE SHIELD CONNECTION SCREW
(CONNECT TO CABLE SHIELD)
Honeywell Sensing and Control
PIN
1
2
3
4
5
6
7
8
9
10
11
12
55