2-Wire Current" Amps 1-Wire Shunt Cal; Figure 12-6: "2-Wire Current Amp W/Single-Wire Shunt Cal" Connection To High-Level Input Channel - Honeywell SC Series Installation Instructions Manual

Signal conditioning self-calibrating digital indicators
Table of Contents

Advertisement

Signal Conditioning, Self Calibrating Digital Indicators
12.2.7 "2-wire Current" Amplifiers with Single-
wire Shunt Cal
Use the following wiring diagram when connecting an amplified
transducer or in-line amplifier with a 2-wire current amplifier to a
High-Level Input channel. Examples of such devices include
transducers with the Option 2p internal amplifier (not
equipped with shunt cal)
transducers with the Option 2p,3d internal amplifier (single-
wire shunt cal)
transducers with the Option 2y internal amplifier (not
equipped with shunt cal)
transducers with the Option 2y,3d internal amplifier (single-
wire shunt cal)

Figure 12-6: "2-wire Current Amp w/Single-Wire Shunt Cal" Connection to High-Level Input Channel

AMPLIFIED TRANSDUCER
OR
IN-LINE AMPLIFIER
DEVICE WITH
CURRENT OUTPUT,
LOOP POWERED,
SINGLE-WIRE
SHUNT CAL
NOTE: SHUNT CALIBRATION
NOT AVAILABLE ON ALL
DEVICES.
54
Honeywell Sensing and Control
(+)SUPPLY
(+)OUTPUT
SHUNT CAL 1
The High-Level Input channel's Configuration Jumpers must be
set as follows for proper operation. See "Excitation and Signal
Jumpers" on page 56.
(+)Excitation supply: "+28 Vdc"
(-)Excitation supply: "GND"
Signal type: "current"
Signal reference: "single ended"
CABLE
008-0608-00
Rev. G,
INSTRUMENT CONNECTIONS
DESIGNATION
+28V
(+)EXCITATION
SHUNT CAL 1
SHUNT CAL 2
0V
(-)EXCITATION
(+)SIGNAL
(-)SIGNAL
(+)ANALOG OUTPUT
(-)ANALOG OUTPUT
N/C
DGND
AUX1
AUX2
NOTE KEYED CONNECTOR
CABLE SHIELD CONNECTION SCREW
(CONNECT TO CABLE SHIELD)
PIN
1
2
3
4
5
6
7
8
9
10
11
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sc2000Sc2001Sc3004

Table of Contents