Chapter 13 Relay Output Channel

13.1 Features

13.1.1 First Channel Installed

The first Relay Output channel installed in an instrument supple-
ments the standard four limits (Limit 1, Limit 2, Limit 3 and Limit
4) . Its four, dry contact relay outputs will mirror the Limit Outputs
pins of the System connector.
In the SYSTEM -> CONFIGURATION sub-menu, channels of this type
are identified as LIMIT 01-04.

13.1.2 Second Channel Installed

The second Relay Output channel installed in an instrument adds
another four limits to the instrument (Limit 5, Limit 6, Limit 7 and
Limit 8). Its relay outputs show the status of these limits.
In the SYSTEM -> CONFIGURATION sub-menu, channels of this type
are identified as LIMIT 05-08.

13.1.3 Third Channel Installed

The third Relay Output channel installed in an instrument adds
another four limits to the instrument (Limit 9, Limit 10, Limit 11 and
Limit 12). Its relay outputs show the status of these limits.
In the SYSTEM -> CONFIGURATION sub-menu, channels of this type
are identified as LIMIT 09-12.

13.1.4 Fourth Channel Installed

The fourth Relay Output channel installed in an instrument adds
another four limits to the instrument (Limit 13, Limit 14, Limit 15
and Limit 16). Its relay outputs show the status of these limits.
In the SYSTEM -> CONFIGURATION sub-menu, channels of this type
are identified as LIMIT 13-16.

13.2 Wiring

The pin-out for the Relay Output channel's 12-pin connector is
shown in the following table.

Table 13-1 Relay Output Channel Pin Connections

Pin
Label
1 (top)
RELAY1 NC
2
RELAY1 C
3
RELAY1 NO
4
RELAY2 NC
5
RELAY2 C
6
RELAY2 NO
7
RELAY3 NC
8
RELAY3 C
9
RELAY3 NO
10
RELAY4 NC
11
RELAY4 C
12
RELAY4 NO
(bottom)

13.3 Setup Procedure

If you are not familiar with operating the instrument in the SETUP
menu mode, see "SETUP Menu mode" on page 7. A listing of all
menu item is given in "Setup Menu Reference" on page 77.
Step 1: Wire to the channel's connector.
See the "Wiring" section earlier in this chapter for details.
Step 2: Use the appropriate Limit Menu to setup the limits.
See "Limits" on page 24 for information about limits.
NOTICE
A SensoCode program running on a Mathematics Virtual
Channel may override the default behavior of the relay out-
puts. Consult the Customer Information Sheet included with
your instrument for details.

13.4 Specifications

RELAY OUTPUT
Quantity and Type
4 form C
Contact rating
0.5 A @ 50 Vac max. (consult factory for
125 Vac max. operation) 1 A @ 30 Vdc
max.
008-0608-00
Rev. G,
Function
Relay 1 normally closed
Relay 1 common
Relay 1 normally open
Relay 2 normally closed
Relay 2 common
Relay 2 normally open
Relay 3 normally closed
Relay 3 common
Relay 3 normally open
Relay 4 normally closed
Relay 4 common
Relay 4 normally open
Honeywell Sensing and Control
Ref.
Pin
2
-
2
5
-
5
8
-
8
11
-
11
65