16 Screws; Evaporator Waterbox Covers; Pressure Testing Waterside Piping; Eddy Current Testing - Trane CenTraVac CDHF Series Installation, Operation And Maintenance Manual

With tracer adaptiview control
Hide thumbs Also See for CenTraVac CDHF Series:
Table of Contents

Advertisement

I I n n s s t t a a l l l l a a t t i i o o n n : : W W a a t t e e r r P P i i p p i i n n g g
Figure 21. Flange screw tightening sequence (16, 20,
or 24 screws)
5
1
9
16
13
12
3
8
7
4
11
14
15
10
2
6

16 screws

1
24
20
16
12
8
4
22
18
14
10
6
24 screws
Flanges with More than 24 Screws
Sequentially tighten the first 12 screws to a snug
tightness, following the numerical sequence as shown
in the following figure. Tighten the next
12 consecutively numbered screws in sequence to the
final torque. Then, apply final torque to the first
12 screws and the screws not yet tightened (i.e.,
unnumbered screws in the following figure). Start with
screw "1" and move progressively around the flange in
a clockwise direction.
Figure 22. Flange screw tightening sequence (more
than 24 screws)
1
5
24
20
16
12
8
4
22
18
14
10
6
2
32
1
5
9
20
13
16
17
12
3
8
7
4
11
18
15
14
19
10
2
6
20 screws
5
9
13
17
21
3
7
11
15
19
2 23
9
13
17
21
3
7
11
15
19
23

Evaporator Waterbox Covers

Ensure that the waterbox head rests tightly against the
tube sheet, and then snugly tighten the 26 bolts in
sequential order as shown in the following figure. If
excessive tube sheet crown prevents the head from
contacting the tube sheet, tighten the bolts located
where the greatest gaps occur. Be sure to use an equal
number of bolt turns from side to side. Then, apply
final torque to each bolt in sequential order.
Figure 23. Evaporator waterbox cover bolt tightening
sequence
21
13
3
7
17
25
9
24
16
6
20
12
2
Pressure Testing Waterside
Piping
N N O O T T I I C C E E
E E q q u u i i p p m m e e n n t t D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w t t h h e e s s e e i i n n s s t t r r u u c c t t i i o o n n s s c c o o u u l l d d r r e e s s u u l l t t i i n n
e e q q u u i i p p m m e e n n t t d d a a m m a a g g e e . .
D D o o n n o o t t o o v v e e r r p p r r e e s s s s u u r r i i z z e e t t h h e e s s y y s s t t e e m m o o r r e e x x c c e e e e d d
d d e e s s i i g g n n p p r r e e s s s s u u r r e e . . A A l l w w a a y y s s p p e e r r f f o o r r m m a a h h y y d d r r o o p p r r e e s s s s u u r r e e
t t e e s s t t w w i i t t h h w w a a t t e e r r p p r r e e s s e e n n t t i i n n p p i i p p i i n n g g a a n n d d w w a a t t e e r r b b o o x x e e s s . .
Waterside design pressure is either 150 psig
(1034.2 kPaG) or 300 psig (2068.4 kPaG); refer to unit
nameplate or to submittal documentation.

Eddy Current Testing

Trane recommends conducting an eddy current
inspection of the condenser and evaporator tubes in
water-cooled chillers every three years. Eddy current
tests are intended to identify defects on or within the
walls of heat exchanger tubing that could lead to in-
service tube failures. Eddy current tests conducted
before a chiller is put into service are considered
"baseline" eddy current tests, and are intended to
establish a reference point to aid in the interpretation of
future eddy current test reports. Many of the anomalies
that can be found through eddy current testing have no
impact on tube life or performance, while others are
severe enough to justify removing the affected tube
from service. Ask your sales account manager for a
copy of the engineering bulletin (CTV-PRB024*-EN) for
clarification of the role of eddy current testing in chiller
1
11
19
5
15
23
10
26
18
8
4
14
22
CDHF-SVX01N-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Centravac cdhg series

Table of Contents