Wiring; Current Transformer And Potential; Transformer Wire Sizing - Trane CenTraVac CDHF Series Installation, Operation And Maintenance Manual

With tracer adaptiview control
Hide thumbs Also See for CenTraVac CDHF Series:
Table of Contents

Advertisement

Customer-supplied Remote Starter Wiring
This information is applicable to Starter 1 for
Compressor 1 as well as Starter 2 for Compressor 2.
Table 16. Standard customer-supplied remote field wiring requirements
Power Supply Wiring to Starter Panel
Starter by Others 3-phase Power Wiring
Starter to Motor Power Wiring
Remote Starter to Chiller Motor Junction Box
Starter to Control Panel 120 Vac Control

Wiring

120 Vac Power Supply (from Starter to
Control Panel)
Power from Control Panel 1Q1
Interlock Relay Signal
Start Contactor Signal
Oil Pump Interlock
Run Contactor Signal
Transition Complete
Low Voltage Circuits Less than 30 Vac
Standard Circuits
Current Transformers (refer to table in

"Current Transformer and Potential

Transformer Wire Sizing," p.
54) (Required)
(b)
Potential Transformers (Required)
Solid State Stater Fault
Notes:
1.
All wiring to be in accordance with National Electrical Code (NEC) and any local codes.
2.
Starter by Others Specification available from your local Trane sales office.
(a)
Wires, lugs, and fuses/breakers are sized based on National Electric Code (NEC) [NFPA 70] and UL 1995.
(b)
Must be separated from 120 Vac and higher wiring.
(c)
Solid State Starter Fault input is used with low- and medium-voltage, customer-supplied solid state starters only.
Current Transformer and
Potential Transformer Wire
Sizing
For customer-supplied starter-to-chiller unit control
panel starter module 1A23; these wires must be
separated from 120 Vac or higher wiring.
54
Starter Panel Terminals
See Starter by Others
Schematic
Starters
T1 through T6 Terminals
Starter Panel Terminals
See Starter by Others
Schematic 5X1-1, 5X1-2, 5X1-
20 (Ground)
5X1-3
5X1-4
5X1-5
5X1-7, 5X1-8
5X1-10
5X1-14
Starter Panel Terminals
5CT4-white, black
5CT5-white, black
5CT6-white, black
5T17-236,237
(b)
5T18-238,239
5T19-240,241
5X1-11
(c)
5X1-12
(For wire estimation purposes, double check the
following table as there are two starters to be wired.)
Motor
T1 through T6
Terminals
Max Terminal Wire
Unit Control Panel
Size (AWG)
Terminations
1X1-1, 1X1-12, 1X1-18
(Ground)
1X1-3, 1A23-J6-3
1A23-J10-1
1A23-J8-1
1A7-J2-4, 1A7-J2-2
1A23-J6-12
1A23-J12-2
Unit Control Panel
Terminations
1A23-J7-1,2
Note: Phasing must
1A23-J7-3,4
be maintained.
1A23-J7-5,6
1A23-J5-1,2
Note: Phasing must
1A23-J5-3,4
be maintained.
1A23-J5-5,6
1A24-J2-1
1A24-J2-2
Table 17. Maximum recommended wire length for
secondary current transformer (CT) leads in
dual CT system
Wire AWG
(a)
8
10
12
14
16
17
18
20
Notes:
1.
Wire length is for copper conductors only.
2.
Wire length is total one-way distance that the CT can be from
the starter module.
Minimum Circuit
(a)
Ampacity
8
40
14
20
14
20
14
20
14
20
14
20
14
20
Maximum Wire Length
Secondary CT Leads
Feet
Meters
1362.8
415.5
856.9
261.2
538.9
164.3
338.9
103.3
213.1
65.0
169.1
51.5
134.1
40.9
84.3
25.7
CDHF-SVX01N-EN