Installation: Mechanical; Operating Environment; Foundation Requirements; Rigging - Trane CenTraVac CDHF Series Installation, Operation And Maintenance Manual

With tracer adaptiview control
Hide thumbs Also See for CenTraVac CDHF Series:
Table of Contents

Advertisement

Installation: Mechanical

Operating Environment

I I m m p p o o r r t t a a n n t t : :
The standard chiller is designed for
INDOOR USE ONLY and as such has
NEMA Type 1 enclosures.
For chillers in unheated equipment
rooms, contact your local Trane Service
Agency for methods to ensure that the
oil temperature is maintained suitable
for proper operation of the chiller.
N N O O T T I I C C E E
E E q q u u i i p p m m e e n n t t D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o p p r r o o t t e e c c t t t t h h e e u u n n i i t t f f r r o o m m f f r r e e e e z z i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n e e q q u u i i p p m m e e n n t t d d a a m m a a g g e e . .
I I f f f f l l u u i i d d h h a a s s b b e e e e n n a a d d d d e e d d t t o o t t h h e e p p i i p p i i n n g g , , t t h h e e u u n n i i t t m m u u s s t t
b b e e p p r r o o t t e e c c t t e e d d f f r r o o m m f f r r e e e e z z i i n n g g . . F F r r e e e e z z e e d d a a m m a a g g e e f f r r o o m m
a a n n u u n n h h e e a a t t e e d d e e q q u u i i p p m m e e n n t t r r o o o o m m i i s s n n o o t t t t h h e e T T r r a a n n e e
c c o o m m p p a a n n y y ' ' s s r r e e s s p p o o n n s s i i b b i i l l i i t t y y . . T T h h e e s s e e a a r r e e i i n n d d o o o o r r u u n n i i t t s s . .
N N O O T T I I C C E E
E E q q u u i i p p m m e e n n t t F F a a i i l l u u r r e e ! !
U U n n i i t t o o p p e e r r a a t t i i n n g g a a t t a a m m b b i i e e n n t t t t e e m m p p e e r r a a t t u u r r e e s s e e x x c c e e e e d d i i n n g g
1 1 0 0 4 4 ° ° F F ( ( 4 4 0 0 ° ° C C ) ) c c o o u u l l d d r r e e s s u u l l t t i i n n A A F F D D / / s s t t a a r r t t e e r r
c c o o m m p p o o n n e e n n t t d d a a m m a a g g e e d d u u e e t t o o t t h h e e p p a a n n e e l l ' ' s s i i n n a a b b i i l l i i t t y y t t o o
d d i i s s s s i i p p a a t t e e h h e e a a t t a a d d e e q q u u a a t t e e l l y y . . F F o o r r C C D D H H F F , , C C D D H H G G , , C C V V H H E E , ,
C C V V H H F F , , C C V V H H G G , , C C V V H H L L , , C C V V H H M M , , a a n n d d C C V V H H S S C C e e n n T T r r a a V V a a c c
c c h h i i l l l l e e r r s s , , u u n n i i t t s s o o p p e e r r a a t t i i n n g g a a t t t t h h e e s s e e t t e e m m p p e e r r a a t t u u r r e e s s
c c o o u u l l d d a a l l s s o o f f a a t t i i g g u u e e t t h h e e u u n n i i t t ' ' s s r r u u p p t t u u r r e e d d i i s s k k , , c c a a u u s s i i n n g g
i i t t t t o o b b r r e e a a k k a a t t a a r r e e d d u u c c e e d d r r e e f f r r i i g g e e r r a a n n t t p p r r e e s s s s u u r r e e ( ( < < 1 1 5 5
p p s s i i g g [ [ < < 1 1 0 0 3 3 . . 4 4 k k P P a a G G ] ] ) ) . .
I I f f a a n n y y o o f f t t h h e e s s e e a a d d v v e e r r s s e e o o p p e e r r a a t t i i n n g g c c o o n n d d i i t t i i o o n n s s a a r r e e
p p r r e e s s e e n n t t , , t t a a k k e e n n e e c c e e s s s s a a r r y y a a c c t t i i o o n n t t o o i i m m p p r r o o v v e e t t h h e e
e e q q u u i i p p m m e e n n t t r r o o o o m m e e n n v v i i r r o o n n m m e e n n t t . .
To ensure that electrical components operate properly,
do NOT locate the chiller in an area exposed to dust,
dirt, corrosive fumes, or excessive heat and humidity.
The maximum ambient temperature for chiller
operation is 104°F (40°C).

Foundation Requirements

Chiller mounting surface must be:
rigid non-warping mounting pads or a concrete
foundation, and
able to support the chiller at its full operating
weight (including completed piping and full
operating charges of refrigerant, oil, and water).
For proper unit operation, the chiller must be level
within 1/16 in. (1.6 mm) over its length and width when
set into place on the mounting surface. Refer to
"Leveling the Unit," p. 22
approximate weights for various chiller sizes and
18
for more information. For
options in pounds and kilograms, refer to
(lb)," p. 16
and
"Weights (kg)," p.
N N o o t t e e : : For specific weight information, refer to the unit
submittal package.
I I m m p p o o r r t t a a n n t t : : Trane will not assume responsibility for
equipment problems resulting from an
improperly designed or constructed
foundation.

Rigging

Lifting is the recommended method for moving
chillers. Suggested lifting arrangements for standard
units are described in
"Standard Chiller Lift," p.
N N o o t t e e : : The lifting beam used for CDHF and CDHG
CenTraVac™ chillers must be at least 23 ft
(7.0 m) long.
W W A A R R N N I I N N G G
H H e e a a v v y y O O b b j j e e c c t t ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n
u u n n i i t t d d r r o o p p p p i i n n g g w w h h i i c c h h c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r
s s e e r r i i o o u u s s i i n n j j u u r r y y , , a a n n d d e e q q u u i i p p m m e e n n t t o o r r p p r r o o p p e e r r t t y y - - o o n n l l y y
d d a a m m a a g g e e . .
E E n n s s u u r r e e t t h h a a t t a a l l l l t t h h e e l l i i f f t t i i n n g g e e q q u u i i p p m m e e n n t t u u s s e e d d i i s s
p p r r o o p p e e r r l l y y r r a a t t e e d d f f o o r r t t h h e e w w e e i i g g h h t t o o f f t t h h e e u u n n i i t t b b e e i i n n g g
l l i i f f t t e e d d . . E E a a c c h h o o f f t t h h e e c c a a b b l l e e s s ( ( c c h h a a i i n n s s o o r r s s l l i i n n g g s s ) ) , , h h o o o o k k s s , ,
a a n n d d s s h h a a c c k k l l e e s s u u s s e e d d t t o o l l i i f f t t t t h h e e u u n n i i t t m m u u s s t t b b e e c c a a p p a a b b l l e e
o o f f s s u u p p p p o o r r t t i i n n g g t t h h e e e e n n t t i i r r e e w w e e i i g g h h t t o o f f t t h h e e u u n n i i t t . . L L i i f f t t i i n n g g
c c a a b b l l e e s s ( ( c c h h a a i i n n s s o o r r s s l l i i n n g g s s ) ) m m a a y y n n o o t t b b e e o o f f t t h h e e s s a a m m e e
l l e e n n g g t t h h . . A A d d j j u u s s t t a a s s n n e e c c e e s s s s a a r r y y f f o o r r e e v v e e n n u u n n i i t t l l i i f f t t . .
W W A A R R N N I I N N G G
I I m m p p r r o o p p e e r r U U n n i i t t L L i i f f t t ! !
F F a a i i l l u u r r e e t t o o p p r r o o p p e e r r l l y y l l i i f f t t u u n n i i t t i i n n a a L L E E V V E E L L p p o o s s i i t t i i o o n n
c c o o u u l l d d r r e e s s u u l l t t i i n n u u n n i i t t d d r r o o p p p p i i n n g g a a n n d d p p o o s s s s i i b b l l y y
c c r r u u s s h h i i n n g g o o p p e e r r a a t t o o r r / / t t e e c c h h n n i i c c i i a a n n w w h h i i c c h h c c o o u u l l d d r r e e s s u u l l t t i i n n
d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y , , a a n n d d e e q q u u i i p p m m e e n n t t o o r r
p p r r o o p p e e r r t t y y - - o o n n l l y y d d a a m m a a g g e e . .
T T e e s s t t l l i i f f t t u u n n i i t t a a p p p p r r o o x x i i m m a a t t e e l l y y 2 2 4 4 i i n n c c h h e e s s ( ( 6 6 1 1 c c m m ) ) t t o o
v v e e r r i i f f y y p p r r o o p p e e r r c c e e n n t t e e r r o o f f g g r r a a v v i i t t y y l l i i f f t t p p o o i i n n t t . . T T o o a a v v o o i i d d
d d r r o o p p p p i i n n g g o o f f u u n n i i t t , , r r e e p p o o s s i i t t i i o o n n l l i i f f t t i i n n g g p p o o i i n n t t i i f f u u n n i i t t i i s s
n n o o t t l l e e v v e e l l . .
N N O O T T I I C C E E
W W i i r r i i n n g g D D a a m m a a g g e e ! !
D D a a m m a a g g e e t t o o u u n n i i t t w w i i r r i i n n g g c c o o u u l l d d r r e e s s u u l l t t i i n n e e q q u u i i p p m m e e n n t t
f f a a i i l l u u r r e e . .
C C a a r r e e m m u u s s t t b b e e t t a a k k e e n n d d u u r r i i n n g g r r i i g g g g i i n n g g , , a a s s s s e e m m b b l l y y a a n n d d
d d i i s s a a s s s s e e m m b b l l y y t t o o a a v v o o i i d d d d a a m m a a g g i i n n g g u u n n i i t t w w i i r r i i n n g g . .

Standard Chiller Lift

1. Insert rigging shackles at the points indicated in the
following figure. A 2.5 in. (63.5 mm)1.25 in. (31.8
"Weights
16, respectively.
18.
CDHF-SVX01N-EN