Table 17. Maximum recommended wire length for
secondary current transformer (CT) leads in dual CT
system (continued)
(a)
Wires, lugs, and fuses/breakers are sized based on National Electric
Code (NEC) [NFPA 70] and UL 1995.
Table 18. Maximum recommended total wire length
for potential transformers (PTs) in a single
PT system
Wire AWG
(a)
8
10
12
14
16
17
18
20
21
22
Notes:
1.
Wire length is for copper conductors only.
2.
Wire length is maximum round trip wire length. The maximum
distance the PT can be located from the starter module is half of
the listed value.
Wires, lugs, and fuses/breakers are sized based on National Electric
(a)
Code (NEC) [NFPA 70] and UL 1995.
CDHF-SVX01N-EN
Maximum Lead Length
Feet
Meters
5339
1627
3357
1023
2112
643
1328
404
835
254
662
201
525
160
330
100
262
79
207
63
C C u u s s t t o o m m e e r r - - s s u u p p p p l l i i e e d d R R e e m m o o t t e e S S t t a a r r t t e e r r W W i i r r i i n n g g
Table 19. Maximum recommended total wire length
(to and from) for PT leads in a dual PT
system
Max Wire Length
Wire AWG
Primary
(a)
Feet
Meters
8
3061
10
1924
12
1211
14
761
16
478
17
379
18
301
20
189
21
150
22
119
Notes:
1.
Wire length is for copper conductors only.
2.
Wire length is maximum round trip wire length. The maximum
distance the PT can be located from the starter module is half of
the listed value.
(a)
Wires, lugs, and fuses/breakers are sized based on National Electric
Code (NEC) [NFPA 70] and UL 1995.
Max Wire Length
Secondary
Feet
Meters
933
711
217
586
447
136
369
281
85
232
177
53
145
111
33
115
88
26
91
70
21
57
44
13
45
34
10
36
27
8