Water Meter Mode
Conditioner
In water meter mode, the controller keeps track of the quantity of water that has flowed through the resin
Operation
bed. When the set point is reached, regeneration is triggered. If time clock backup is set and the capacity
has not been exhausted but the days since last regeneration is greater than time clock backup, setting the
filter will regenerate.
Remote Display Control
The remote display control displays the current status of the water filter and allows for remote control. It
can be located up to 200 feet away from the filter (depending upon building construction materials). The
wireless remote displays information about filter performance, problems, remaining and allows remote
control for regeneration.
The wireless remote control is designed to communicate at 915 MHz and to work without interference with
other 915 MHz devices such as cordless telephones and baby monitors.
Modem
The modem allows for the system to be remotely monitored detecting problems before they occur and to
keep the system software up to date with the latest advances.
Manual Regeneration
Manual regeneration can be initiated via the filter control valve or remote display. Manual regeneration
can be initiated to begin regeneration immediately or that night.
Settings
The Culligan Automatic Water Filter is designed to perform efficiently on a wide range of water supplies.
In order to ensure proper operation of the filter, and before initiating the initial recharge and putting the
unit into service, the following settings need to be made.
Backwash
The backwash setting is important in that backwashing expands and loosens the media bed. This flushes
away the particulate matter that has accumulated in the bed. The backwash interval is preset at the fac-
tory for 10 minutes, which is adequate for most water supplies. It is recommended that the backwash
cycle last just long enough so that the effluent from the drain line is clear. Backwash too long and water is
wasted, not long enough and the tank becomes fouled with sediment.
Pause Cycle
Because this Automatic Water Filter shares it timer with other water conditioning products, it momentarily
stops in a pause cycle. This setting is used in other controls for the eduction and rinsing of salt, or other
regenerant chemicals. The pause cycle is factory set at 2 minutes.
Rapid Rinse
The rapid rinse setting settles and compacts the media after backwashing and flushes any residual par-
ticulate matter from the bottom of the filter bed before returning the filter to the service position. The rapid
rinse setting is factory set at 10 minutes.