6.2 - Configuration menu

Icon
Displayed text*
General Configuration
Pump Configuration
User Configuration
Reset Configuration
Schedule Menu
Holiday Menu
Broadcast Menu
Date/Time configuration
Control Identification
*Depends on the selected language (English by default).
CAUTION: Since specific units may not include additional features, some tables may contain parameters that cannot be
configured for a given unit.
General Configuration Menu – GEN_CONF
No.
Name
Status
1
lead_cir
0 to 2
2
3
4
seq_typ
0 to 2
5
6
7
ramp_sel
no/yes
8
off_on_d
1 to 15
9
nh_start
00:00
10
nh_end
00:00
11
nh_limit
0 to 100
12
bas_menu
0 to 3
13
14
15
16
17
lim_sel
0 to 2
18
19
20
21
lim_mx
0 to 20
22
lim_ze
0 to 20
23
curr_sel
no/yes
24
curr_ful
0 to 4000
Description
General configuration
Pump configuration
User configuration
Reset configuration
Schedule menu
Holiday menu
Broadcast configuration
Date/time configuration
Control identification
Default
Unit
Displayed text*
0
-
Cir Priority Sequence
0=Auto, 1=A Prio
2=B Prio
0
-
Loading Sequence
0=Equal, 1=Staged
2=Smart
no
-
Ramp Loading Select
1
min
Unit Off to On Delay
00:00
hour
Night Mode Start Hour
00:00
hour
Night Mode End Hour
100
%
Night Capacity Limit
0
-
Basic Menu Configuration
0 = All Access
1 = no alarm menu
2 = no setpoint menu
3 = 1 + 2
0
-
Demand Limit Type Select
0 = None
1 = Switch Control
2 = 4-20mA Control
0
mA
mA For 100% Demand Limit
10
mA
mA For 0% Demand Limit
no
-
Current Limit Select
2000
A
CurrentLimit at 100%
Associated table
GEN_CONF
PUMPCONF
USERCONF
RESETCFG
SCHEDULE
HOLIDAY
BROCASTS
DATETIME
CTRL_ID
Description
Circuit priority
0 = Automatic circuit selection
1 = Circuit A priority
2 = Circuit B priority
Loading sequence (see also section 7.12)
0 = Equal loading sequence
1 = Staged loading sequence
2 = Smart loading sequence
Ramp loading selection
Unit Off to On delay
Night mode start time
Night mode end time
Night capacity limit
Basic menu configuration
0 = All access
1 = No alarm menu
2 = No setpoint menu
3 = No alarm and no setpoint menu
Demand limit selection
0 = None
1 = Switch Control
2 = 4-20mA Control
100% demand limit (mA)
0% demand limit (mA)
Current limit selection
Current limit at 100%
19