Maintenance - Carrier Touch Pilot Manual

For 61xwhze heat pumps
Table of Contents

Advertisement

No.
Code
Alarm description
133
2112
Compressor B Unable to stop motor
134
2113
Compressor B Phase reversal
135
2114
Compressor B MTA configuration fault
136
2115
Compressor B Configuration switch
mismatch
137
2116
Compressor B Unexpected switch setting
change
138
2117
Compressor B Power on reset
139
2118
Compressor B UL 1998 critical section
software error
140
2119
Compressor B UL 1998 current measure
dual channel mismatch
141-
3101-
Compressor C alarms
159
3119

9 - MAINTENANCE

In order to ensure the optimal operation of the equipment
as.well.as.the.optimization.of.all.the.available.functionalities,.
it.is.recommended.to.activate.a.Maintenance.Contract.with.
your.local.Carrier.Service.Agency..
The contract will ensure your Carrier equipment is regularly
inspected. by. Carrier. Service. specialists,. so. that. any.
malfunction is detected and corrected quickly, and no serious
damage can occur to your equipment.
The.Carrier.Service.Maintenance.Contract.represents.not.
only the best way to ensure the maximum operating life of
your equipment, but also, through the expertise of Carrier
qualified.personnel,.the.optimal.tool.to.manage.your.system.
in.a.cost-effective.manner.
Reset type
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Not applicable to this unit
Action taken
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Unit shuts down
Possible cause
Incorrect wiring or
defective contactor
-
MTA configuration
incorrect or defective
TCPM board
Configuration switch S1
incorrect wiring or
defective TCPM board
As above
Verify that power supply
cuts have occurred
Power network noise or
defective TCPM board
Power network noise or
defective TCPM board
35