5.7 - Configuration menu
The.Configuration.menu.gives.access.to.a.number.of.user-
modifiable.parameters.such.as.pump.configuration,.schedule.
menu, etc.
General configuration screen
To.access.the.General.configuration.screen,.go.to.the.
Configuration.menu.and.select.Genunit Config.
1
2
1
Save
2
Cancel
3
Previous page
4
Next page
Press.the.field.corresponding.to.the.parameter.to.be.modified.
and introduce all the necessary changes.
Once all the necessary modifications have been made, press
to confirm or
to cancel changes.
5.8 - Override screen
The override screen provides the option to issue the command
overriding the current operation of the unit.
To access the override screen, press the forceable point of
the data screen.
to remove the forced point.
Press
to set or
14
6 - WEB CONNECTION
6.1 - Web interface
The Touch Pilot Junior control can be accessed via a web
browser (Internet Explorer, Mozilla Firefox, etc.).
Connection is from a PC using a web browser with Java.
IMPORTANT: Use firewalls and VPN for secure connection.
6.2 - Opening the web interface
To access the Touch Pilot Junior control, enter the IP address
of the unit in the address bar of the web browser.
Unit default address: 169.254.0.1.
This address can be changed.
IMPORTANT: Only two web connections can be authorised
3
4
at the same time.
For security reasons the unit cannot be started / stopped via
the web interface. All other operations, including monitoring
unit.parameters.or.unit.configuration,.can.be.performed.via.
the web browser interface.
6.3 - Web browser settings
Minimum.web.browser.configuration:
• Internet Explorer (version 8 or higher) or Mozilla Firefox
• Java platform (version 6 or higher). In the control panel,
IMPORTANT: Two users can be connected simultaneously
with no priority between them. Note the last modification
is always taken into account.
(version 26 or higher). In the advanced connection
options add the unit IP address to the exceptions list. Do
not use a proxy server.
clear.the.Keep.temporary.files.on.my.computer.check.box.
and use a direct connection.