7.15 - Master/Slave assembly

Two.units.can.be.linked.to.create.the.master/slave.assembly..
The master unit can be controlled locally, remotely or by
network.commands..Master/slave.assembly.must.be.validated.
in.order.to.start.the.master/slave.chiller.operation.
All.control.commands.to.the.master/slave.assembly.(start/
stop, setpoint selection, heating/cooling operation, load
shedding,.etc.).are.handled.by.the.unit.which.is.configured.
as the master. The commands are transmitted automatically
to.the.slave.unit..If.the.master.chiller.is.turned.off.while.the.
master/slave.function.is.active,.then.the.slave.chiller.will.be.
stopped..Under.certain.circumstances,.the.slave.unit.may.be.
started.first.to.balance.the.run.times.of.the.two.units.
In. the. event. of. a. communication. failure. between. the. two.
units, each unit will return to an autonomous operating mode
until the fault is cleared. If the master unit is stopped due to
an.alarm,.the.slave.unit.is.authorised.to.start.
NOTE: Master/slave assembly can be configured only by
Carrier service technicians.

7.16 - Energy Management Module (EMM)

The.energy.management.module.enables.to.control.the.level.
of. energy. consumption,. providing. users. with. information.
such as current unit status, compressors operating status, etc.
This option requires the installation of an additional SIOB
board.
Description
Connector *
Occupancy
DI-01, 77-78
override control
Demand limit
DI-02,
switch 2
73A-74A
Customer
DI-03,
interlock
34A35A
Ice storage
DI-04, 75-76
Space
AI-01,
temperature
71A-72A
Capacity limit
AI-10, 67-68
control
Compressor A
DO-01,
37A1-38A1
Compressor B
DO-02,
37B1-38B1
Chiller ready
DO-04,
30A-31A
Chiller in alert
DO-05,
30B-31B
Chiller
DO-06, 30-31
shutdown
Unit capacity
A0-01,
79+-79-
* Connector type:
DI = Digital Input
AI = Analogue Input
DO = Digital Output
AU = Analogue Output
28
Remarks
If the contact is closed in Remote
mode, the unit goes into the occupied
mode
If the contact is closed, the second
capacity limit switch is active
Permits immediate unit shutdown
(Remote mode only)
If the contact is closed, the unit starts
the ice storage mode
Active setpoint reset via space
temperature control
Active setpoint reset via unit capacity
control (4-20 mA)
Output active if compressor A is
operating
Output active if compressor B is
operating
Relay output active when the unit is
ready to operate
Relay output active when the alert is
tripped
Relay output active when the unit is
stopped due to an alarm
Capacity running output (0 to10 VDC)

7.17 - Schedule setting

The.control.incorporates.two.time.schedules,.where.the.first.
one (OCCPC01S) is used for controlling the unit start/stop,
whereas the second one (OCCPC02S) is used for controlling
the dual setpoint.
The first timer program (schedule. 1). provides. a. means. to.
automatically switch the unit from an occupied mode to an
unoccupied mode: the unit is started during occupied periods.
The second timer program.(schedule.2).provides.a.means.to.
automatically switch the active setpoint from an occupied
setpoint to an unoccupied setpoint: cooling or heating setpoint 1
is used during occupied periods, cooling or heating setpoint 2
during unoccupied periods.
The control offers the user the possibility of setting eight
occupancy periods where each occupancy period includes the
following.elements.to.be.defined:
• Day of the week: Select the days when the period is
occupied.
• Occupancy time ("occupied from" to "occupied to"):
Set occupancy hours for the selected days.
• Timed Override Extension: Extend the schedule if
necessary. This parameter can be used in the case of
some.unplanned.events..Example: If the unit is normally
scheduled to run between 8:00 to 18:00, but one day you
want the air-conditioning system to operate longer, then set
this timed override extension. If you set the parameter to
"2", then the occupancy will end at 20:00.
To set the unit start/stop schedule
1. Go to the Main menu.
2. Navigate.to.the.Configuration.menu.(logged-in.users.only).
and select Schedule Menu (SCHEDULE).
3. Go to OCCPC01S.
4. Select appropriate check boxes to set the unit occupancy on
specific.days.
5. Define.the.time.of.occupancy.
6. When the time schedule is set, the selected period will be
presented in the form of the green band on the timeline.
7. Press the Save.button.to.save.your.changes.or.the.Cancel
button.to.exit.the.screen.without.making.modifications.
3
4
1
Selection of days for the time schedule
2
Start/end of the schedule
3
Save
4
Cancel
5
Previous time period
6
Next time period