Wiring - Omega CN8200 Series User Manual

1/16 din temperature & process controllers
Table of Contents

Advertisement

Dimensions
Figure 2. Case Dimensions
Prior to mounting the Series CN8200 in your panel, make
sure that the cutout opening is of the right size, 1.771" x
1.771" (45 mm x 45 mm), and deburred to enable a smooth
fit. A minimum of 4" (100 mm) of depth behind the panel is
required.
Mounting
Figure 3. Series CN8200 Mechanical Components
Insert the Series CN8200 through the front panel cutout and
When properly installed
slide the mounting collar back onto the unit from behind the
through a NEMA
panel. Push the mounting collar up tight to the back of the
enclosure, the integrity
mounting panel.
of the enclosure will be
maintained and will
remain "Watertight."
Bezel
Grips
Gasket
Case Clip
Customer Panel
2

Wiring

IMPORTANT: All electrical wiring connections should be made
only by trained personnel, and in strict accordance with the
National Electrical Code and local regulations.
The Series CN8200 controller has built-in circuitry to reduce
the effects of electrical noise (RFI) from various sources.
However, power and signal wires should always be kept
separate. We recommend separating connecting wires into
bundles: power; signal; alarms; and outputs. These bundles
should then be routed through individual conduits. Shielded
sensor cables should always be terminated at one end only.
If additional RFI attenuation is required, noise suppression
devices such as an R.C. snubber at the external noise source
may be used.
Figure 4. Contact Identification
ALARM & COMM.
N.O.
RCV
B (-)
N.O.
1
OUTPUT 1
C
2
13
N.C.
3
11
N.O.
4
OUTPUT 2
C
5
L1
100 - 250 V 50/60 Hz
100 - 250 Vdc (Auto Polarity)
24 Vac/Vdc (Auto Polarity)
3
COM
A1
RS 232
XMT
A (+)
RS 485
232/485
COM
ALARM
6
GND
A2
COMM.
N.O.
7
14
8
12
SENSOR
RTD
9
INPUT
T/C
10
L2
&