Download Print this page

Carrier 59SE5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 75

Single stage 4-way multipoise condensing gas furnace 22vac 50 hz series 100

Advertisement

SEQUENCE
OF OPERATION
NOTE:
Furnace
control
must be grounded
for proper
operation
or
control
will lock
out. Control
is grounded
through
green/yellow
wire routed
to gas valve
and manifold
bracket
screw.
Using the
schematic
diagram
in Fig. 65, follow
the sequence
of operation
through
the different
modes.
Read and follow
the wiring
diagram
very carefully.
NOTE:
If a power
interruption
occurs during
a call for heat (W),
the control
will start a 108-sec
blower-only
ON period
two sec
after power
is restored,
if the thermostat
is still calling
for gas
heating.
The
Green
LED
light
will flash
Code
1+2
during
the
108-sec
period,
after which
the LED will be flashing
a heartbeat,
as long
as no faults
are detected.
After
the 108-sec
period,
the
furnace will respond
to the thermostat
normally.
The blower
door
must
be installed
for power
to be conducted
through
the blower
door
interlock
switch
ILK
to the
furnace
control
CPU,
transformer
TRAN,
inducer
motor
IDM,
blower
motor BLWM,
hot-surface
igniter HSI, and gas valve GV.
1. Heating
See Fig. 36 for thermostat
connections.
The wall
thermostat
"calls for heat,"
closing
the R-to-W
circuit.
The furnace
control
performs
a self-check,
verifies
the pressure
switch
contacts
LPS
and HPS
are open,
and
starts the inducer
motor IDM.
a. Inducer
Prepurge
Period-
As the inducer
motor IDM
comes up to speed, the HUM terminal
is energized
at 220v,
and the low pressure
switch
contacts
LPS close to begin
an 18 second
prepurge
period,
and 24 vac is supplied
for
a field installed
humidifier
at the HUM
24 vac terminal.
The high pressure
switch
contacts
HPS are ignored
until
one nfinute after the gas valve is energized.
b. Igniter Warm-Up-
At the end of the prepurge
period, the
Hot-Surface
igniter HSI is energized
for a 20-sec
igniter
warm-up
period.
c. Trial-for-Ignition
Sequence-
When
the
igniter
warm-up
period
is completed,
the main gas valve
relay
contacts
GVR close to energize
the gas valve GV, the gas
valve opens.
The gas valve
GV pernfits
gas flow to the
burners
where it is ignited
by the HSI. Five sec after the
GVR closes, a 2-sec flame proving
period begins. The HSI
igniter will remain
energized
until the flame is sensed or
until the 2-sec flame proving
period begins.
d. Flame-Proving-
When the burner
flame is proved
at the
flame-proving
sensor electrode
FSE, the furnace
control
CPU begins the blower-ON
delay period and continues
to
hold the gas valve
GV open.
If the burner
flame is not
proved
within two sec, the control CPU will close the gas
valve GV, and the control CPU will repeat the ignition
se-
quence for up to three more Trials-For-Ignition
before go-
ing to Ignition-Lockout.
Lockout
will be reset automatic-
ally after 3-1/2
hours or by momentarily
interrupting
220
vac power to the furnace,
or by interrupting
24 vac power
at 24VAC
or COM to the furnace
control
CPU (not at W,
G, R, etc.).
If flame is proved
when
flame should
not be present,
the
furnace
control
CPU will lock out of Gas-Heating
mode
and operate
the inducer motor IDM until flame is no longer
proved.
e. Blower-On
Delay-
If the burner
flame is proven,
the
blower motor is energized
on HEAT speed 30 sec after the
gas valve GV is energized.
Sinmltaneously,
the electronic
air cleaner ternfinal
EAC is
energized
and remains energized
as long as the blower
mo-
tor BLWM
is energized.
f. Heat-Off
Delay-
When
the thermostat
is satisfied,
the
R-to-W
circuit is opened, de-energizing
the gas valve GV,
stopping
gas flow to the burners, and de-energizing
the hu-
midifier
terminal
HUM 24 VAC. The inducer
motor IDM,
and HUM
ternfinal
will remain
energized
for an 18-sec
post-purge
period.
The blower
motor
BLWM
and air
cleaner
ternfinal EAC will remain
energized
for 108, 144,
180, or 216 sec (depending
on the heat-OFF
delay selec-
tion).
Note board selections
are shown
as 90, 120, 150,
180. The furnace control CPU is factory-set
for a 144-sec
heat-OFF
delay.
2. Cooling
Mode
The thermostat
"calls for cooling."
See Fig. 36 for thermo-
stat connections
The
thermostat
closes
the
R-to-G-and-Y
circuits.
The
R-to-Y
circuit
starts
the
outdoor
unit,
and
the
R-to-G-and-Y
circuits
start
the
furnace
blower
motor
BLWM on COOL
speed.
The electronic
air cleaner
ternfinal
EAC is energized
with
220 vac when the blower
motor BLWM is operating.
When
the thermostat
is satisfied,
the R-to-G-and-Y
circuits
are
opened.
The outdoor
unit will stop, and the furnace
blower
motor BLWM
will continue
operating
on the COOL
speed
for an additional
108 sec.
Jumper
J2 can be cut to reduce
the cooling-OFF
delay to 6 seconds.
3. Continuous
Blower
Mode
When
the R-to-G
circuit
is closed
by the thermostat,
the
blower
motor
BLWM
will
operate
on HEAT
speed
and
EAC
ternfinal
is energized
as long
as the blower
motor
BLWM
is energized..
During
a call for heat, the blower
BLWM will stop during
igniter
warm-up
(20 sec), ignition
(8 sec), and blower-ON
delay (30 sec), allowing
the furnace
heat exchangers
to heat up more quickly,
then restarts
at the
end of the blower-ON
delay period
at HEAT speed.
In heating,
the furnace
control
CPU will continue
running
the blower
motor BLWM
at HEAT speed
after the selected
blower-OFF
delay period is completed.
When the thermostat
"calls for cooling",
the blower
motor
BLWM
will operate
at COOL
speed. When
the thermostat
is satisfied,
the blower
motor
BLWM
will operate
an addi-
tional
108
sec on COOL
speed
before
reverting
back
to
continuous-blower
speed.
When
the
R-to-G
circuit
is opened,
the
blower
motor
BLWM will continue
operating
for an additional
6 sec, if no
other function
requires
blower
motor BLWM
operation.
4. Heat Pump
Mode
Change
Heat Pump
to:
HEAT PUMP
MODE.
When in-
stalled with
a heat pump,
the furnace
control
automatically
changes
the tinting
sequence
to avoid
long blower
off times
during
demand
defrost
cycles.
When the R-to-W
and-Y
or
R-to-W-and-Y-and-G
circuits
are energized
the furnace
control
CPU
will continue
to turn
on the blower
motor
BLWM
at HEAT
speed,
and begin
a heating
cycle.
The
blower
motor
BLWM
will remain
on until the end of the
prepurge
period,
then shut off for 24 sec then come back on
at HEAT speed.
When
the W input
signal disappears,
the
furnace
control
begins
a normal
inducer
post-purge
period
and the blower
switches
to COOL
speed after a 3 sec delay.
If the R-to-W-and-Y-and-G
signals
disappear
at the same
time, the blower
motor BLWM will remain on for the selec-
ted blower-OFF
delay period.
If the R-to-W-and-Y
sig-
nals
disappear,
leaving
the
G signal,
the
blower
motor
BLWM
will continue
running
the blower
motor
BLWM
at
HEAT speed after the selected
blower-OFF
delay period is
completed.
Component
Self-Test
Refer to page 66 for instructions.
75

Advertisement

loading