Carrier 59SE5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 61

Single stage 4-way multipoise condensing gas furnace 22vac 50 hz series 100

Advertisement

SERVICE
To perform status coderecall/component
test,thecontrol mustbeinidle mode (nocallsfor heat,
cool,or fanwiththe blower off)displaying a "Heartbeat". Status coderecall/component
testcanbe
performed in oneoftwoways:
1. Briefly (2.3seconds) c onnect theTEST/IWlN terminal tothe "C"thermostat terminal withajumper wire.
(NOTE:Ifconnected f or more than5-6seconds s tatuscode10willflashbutit willnotoverwrite t he previous
statuscode).
OR
2. Briefly remove thenreconnect onelimit w ire(main or rollout s witch).
(NOTE:If limitwireis disconnected for more than5-6seconds statuscode 4 willflashandthe previous s tatus code
willbelost).Afterthestatus codeisflashed 4 times thecomponent testwillbegin(see"Component TestSequence"
below). If noprevious s tatuscodeis available t hecontrol w illnotflasha statuscodeandwillimmediately startthe
component test. S tored statuscodes areerased automatically after86hours.
EACHOFTHE FOLLOWING STATUS CODESISA SINGLE ORTWODIGITNUMBER WiTH
THEFIRSTNUMBER DETERMINED BYTHENUMBEROFSHORTFLASHES ANDTHE
SECOND NUMBERAFTERTHEPLUS(+) SIGNiSTHENUMBEROFLONGFLASHES.
LED STATUS CODES
HEARTBEAT(bright-dim) - Control has24VAC power
2
PRESSURE SWITCH DIDNOTOPEN Check for:- Obstructed p ressure tubing.-Pressure s witchstuckclosed.
3
PRESSURE SWITCH DIDNOTCLOSE ORREOPENED - If LPSopenlonger t han6 minutes, i nducer s huts
offfor 18minutes beforeretry.If HPBremains open for 72seconds aftergasvalvecloses(afterthree
succesive tdals), t henfurnacecontrol will lockout f or3-1/2hoursbeforeretry.
- Excessive wind
- Proper v entsizing
- Defective inducer m otor
- Lowinducer v oltage (220VAC)
- Defective p ressure switch
- Inadequate combusfien a irsupply
- Disconnected or obstructed p ressure t ubing
- Lowinletgaspressure (if LGPSused)
- Restricted vent
- Condensate drainage restricted or blocked
If it opens during blower o n-delay period, b lower w illcomeonfor theselected blower o ff-delay.
4
LIMITCIRCUIT FAULT-Indicates a limitorflamerolloutis open.
Blower will runfor 5 minutes or until o penswitchremakes w hichever is longer.Ifopenlonger t han
3-1/2minutes, c odechanges t o lockout # 7. If open lessthan3-1/2minutes status code#4continues t oflash
untilblower s hutsoff.
Flame rollout s witch requires manual r eset.Check for:
- Restricted v ent
- Properventsizing
- Looseblower w heel
- Excessive w ind - Dirty filter or restricted ductsystem
- Defective blower m otor or capacitor - Defective s witchor connections
- Inadequate combusfion a irsupply (Flame Roll-out S witch open)
5
ABNORMAL FLAME-PROVING
SIGNAL-Flame is proved whilegasvalveis de-energized. Inducer w ill
rununtilfaultis cleared. Check for:
- Leakygasvalve
- Stuck-open g asvalve
6
IGNITION PROVING FAILURE - Control w illtrythreemoretimesbeforelockout # 6+1occurs.
Ifflamesignallostduringblower o n-delay period, blowerwillcomeonforthe selected blower o ff-delay.
Check for:- Flamesensor m ustnotbegrounded - Oxidebuildup onflamesensor(clean withfinesteelwool
- Properflamesensemicroamps ( .5microamps D .C.min.,4.0 - 6.0 nominal).
- Gasvalvedefective or gasvalveturnedoff
- Manual v alveshut-off - Lowinletgaspressure
- Defective HotSurface Ignitor-Control g round continuity - Inadequate flamecarryover or roughignition
- Green/Yellow w ireMUST beconnected tofurnacesheet m etal.
7
LIMITCIRCUIT LOCKOUT- L ockout o ccurs if the limitor flamerollout i s openlonger t han3-1/2minutes.
- Control w ill autoreset a fter3-1/2hours.- Refer t o #4.
8
GASHEATING LOCKOUT- C ontrol w illNOTautoreset. C heck for:
- Mis-wired gasvalve
- Defective c ontrol ( valverelay)
10
POLARITY- L inevoltage (220VAC) polarity reversed. - If twinned, refer to twinning kitinstructions.
1+2
BLOWER ONAFTER POWER UP (220VAC or 24VAC) - Blower runsfor 108seconds, i f unitis powered u p
duringa callforheat(R-Wclosed) o r (R-W)opens duringblower o n-delay.
6+1
IGNITION LOCKOUT - Control w ill auto-reset after3-1/2hours. Refer t o #6.
OFF SECONDARYVOLTAGEFUSEISOPENCheckfor:
. Doorswitchnotclosed
-220VAC at L1andNeutral, 24VACat 24VAC REDandCOMBLUE, 24VFuse 3A
- Shortcircuitinsecondary voltage (24VAC) w iring.
ON
CONTROL CIRCUITRY LOCKOUT A uto-reset after72minutes lockout d ueto;
SOLID - Gasvalverelaystuckopen
- Flame sensecircuit f ailure
- Software checkerror
Reset p ower to clearlockout.Replace c ontrol i f statuscode repeats.
COMPONENT
TEST
Gas valve and humidifierwill not be turnedon. Componentswill be tested insequence as follows:
Inducermotor will run for entire componenttest, and the following componentsare ON for
12-18 seconds each individually; hot surface igniter, FAN(if equipped),
HEATspeed, COOL speed.
Fig. 56 - Service
Label
Information
A12561
61