Outdoor Unit Electronic Expansion Valve - Fujitsu ASTG18KMTC Service Instruction

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for ASTG18KMTC:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 3

Outdoor unit Electronic Expansion Valve

( EEV )
Check Point 1 : Check Connections
Check connection of connector
( Loose connector or open cable )
EXPANSION
VALVE COIL
RED
1
1
BLUE
2
2
ORANGE
PMV
P30
3
3
YELLOW
4
4
WHITE
5
5
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Lead wire
White - Red
Yellow - Red
Orange - Red
Blue - Red
If Resistance value is abnormal, replace EEV.
Check Point 5 : Check Opening and Closing Operation of Valve
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
CLOSE
Example : Hot Gas
Pipe (In)
Check Point 6 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in
but if there is a difference as shown in
Pipe (In)
Resistance value
46
4
at
20°C
Pipe (Out)
, there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (Out)
Check Point 3 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
Check Point 4 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
12V
RED
1
1
BLUE
2
2
ORANGE
3
3
P30
YELLOW
4
4
WHITE
5
5
If it is open,
it has no temp. difference between Inlet and Outlet.
OPEN
Example : Hot Gas
Pipe (In)
Pipe (In)
02-55
PMV
Pipe (Out)
,
Pipe (Out)
DC