Outdoor Unit Main Pcb Model Information Error - Fujitsu ASTG18KMTC Service Instruction

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for ASTG18KMTC:
Table of Contents

Advertisement

Trouble shooting 9
OUTDOOR UNIT Error Method:
Outdoor unit main PCB model
information error
Detective Actuators:
Outdoor unit Main PCB
Forecast of Cause:
1. External cause (Noise, temporary open, voltage drop)
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YES
YES
Check Point 2 : Replace Main PCB
Change Main PCB.
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit
: Operation lamp: 6 times Flash, Timer lamp: 2 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 62]
Detective details:
Access to EEPROM failed due to some cause after outdoor unit started.
NO
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related
cables near the power line.
02-19