Room Temp. Sensor Error - Fujitsu ASTG18KMTC Service Instruction

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for ASTG18KMTC:
Table of Contents

Advertisement

Trouble shooting 6
INDOOR UNIT Error Method:
INDOOR UNIT

Room temp. sensor error

Detective Actuators:
Indoor unit Controller PCB
Room temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 :
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Check Point 3 :
Make sure circuit diagram of indoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
BLACK
2
2
CN1
BLACK
3
3
BLACK
4
4
If the voltage does not appear, replace Controller PCB.
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit
ERROR CODE : [E : 41]
Detective details:
When Room Temperature Thermistor open or short-circuit is detected.
2.Thermistor failure
-10°C
-5°C
0°C
58.2
44.0
33.6
30°C
35°C
40°C
8.0
6.5
5.3
THERMISTOR
(PIPE)
THERMISTOR
(ROOM TEMP.)
: Operation lamp: 4 times Flash, Timer lamp: 1 time Flash
Economy lamp: Continuous flash.
3. Controller PCB failure
5°C
10°C
15°C
25.9
20.2
15.8
45°C
4.4
02-16
20°C
25°C
12.5
10.0