3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
1st defrost
Compressor
Compressor
integrating
integrating
operation:
operation:
Over 22 min.
Over 62 min.
Outdoor
Outdoor
heat exchanger
heat exchanger
temperature:
temperature:
Below - 9°C
Below - 5°C
Heating operation start : Compressor ON
2nd and later defrost
Compressor integrating
operation:
Over 40 min.
.outside temp. > -10°C
=
Outdoor heat exchanger temp.
< -17°C
.outside temp. < -10°C
1 Outdoor heat exchanger temp.
< -20°C
2 Outdoor heat exchanger temp.
< Outside air temp -7°C.
3 Tn-Tn10< -5°C (and Tn< -6°C)
4 Tn-Tnb< -2°C (and Tn< -6°C)
Defrost start
Defrost Indicator:
[Operation lamp]
6 sec ON / 2 sec OFF
Outdoor heat exchanger temperature:
Over +16°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-16
(Not defrosted for 10 minutes)
Compressor
OFF count :
40 times
(Less than 10min.)
Integrating defrost
(Constant monitoring)
Compressor
Compressor
integrating
integrating
operation:
operation:
Over 240 min.
Over 215 min.
Outdoor
Outdoor
heat exchanger
heat exchanger
temperature:
temperature:
Below - 3°C
Below - 5°C