Defrost Flow Chart; Heating Operation Start : Compressor On - Fujitsu ASTG18KMTC Service Instruction

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for ASTG18KMTC:
Table of Contents

Advertisement

3. Defrost Flow Chart

The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
1st defrost
Compressor
Compressor
integrating
integrating
operation:
operation:
Over 22 min.
Over 62 min.
Outdoor
Outdoor
heat exchanger
heat exchanger
temperature:
temperature:
Below - 9°C
Below - 5°C

Heating operation start : Compressor ON

2nd and later defrost
Compressor integrating
operation:
Over 40 min.
.outside temp. > -10°C
=
Outdoor heat exchanger temp.
< -17°C
.outside temp. < -10°C
1 Outdoor heat exchanger temp.
< -20°C
2 Outdoor heat exchanger temp.
< Outside air temp -7°C.
3 Tn-Tn10< -5°C (and Tn< -6°C)
4 Tn-Tnb< -2°C (and Tn< -6°C)
Defrost start
Defrost Indicator:
[Operation lamp]
6 sec ON / 2 sec OFF
Outdoor heat exchanger temperature:
Over +16°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
01-16
(Not defrosted for 10 minutes)
Compressor
OFF count :
40 times
(Less than 10min.)
Integrating defrost
(Constant monitoring)
Compressor
Compressor
integrating
integrating
operation:
operation:
Over 240 min.
Over 215 min.
Outdoor
Outdoor
heat exchanger
heat exchanger
temperature:
temperature:
Below - 3°C
Below - 5°C

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Astg22kmtcAstg24kmtcAotg18kmtcAotg22kmtcAotg24kmtc