The wiring table gives the wire run length from the control panel
to the keypad for various gauges of wire. Wire run lengths are
based on the maximum current drawn by the keypad. (All lights
ON).
If two wires of the same gauge are paralleled, the run length can
be doubled. eg. If 8 #22 AWG wires are used, 2 red, 2 blk, 2 grn
and 2 yel, the run length would go from 420' to 840' (127 to 254
m).
Wiring Chart PC1500RK
Wire Gauge Max. Run Length
(AWG)
24
22
20
19
18
Fire Zone Wiring
Any one of the 6 zones may be programmed as a Fire Loop. See
Programming Guide Section [11].
Smoke detectors should be the latching type and have N.O.
alarm initiating contacts. Power wiring from the AUX + /
PGM terminals should be supervised using an RM-1 relay
after the last smoke detector. The RM-1 N.O. contacts
(closed with power applied) should be wired in series with
the alarm initiating end-of-line resistor so that should power
to the detector(s) fail, a fire loop trouble will be initiated.
AUX +
PGM
Z1
-
DETECTOR
IN
POWER
12VDC
+
OUT
WHT
LATCHING 4-WIRE
SMOKE DETECTOR
5600Ω 0.5W
END OF LINE
RESISTOR
Alarm Initiating Loop Wiring Chart
Wire
AWG
AWG
Gauge
14
16
Distance
19 800' 12 450' 7800'
to EOL
6035m 3794m 2377m 1889m 914m
Resistor
Figures based on maximum loop resistance of 100 ohms.
Keypad to Panel
260' (79m)
420' (127m)
660' (200m)
830' (252m)
1050' (318m)
COM
RM-1 POWER LOOP
SUPERVISORY RELAY
12VDC 35mA MAX.
BLK
WHT
IN
-
N.O.
OUT
ALM
+
RED
GRN
ALARM INITIATING
LOOP; RESISTANCE 100Ω
AWG
AWG
AWG
18
19
22
6200'
3000'
1900'
579m
Fire Zone Power Wiring Chart
Current
mA
50
100
200
300
400
Wire run distances are in feet / meters from the Aux. +/- terminals to the
End-Of-Line Power Supervisory Relay. Figures are based on 12 VDC at
the Aux +/- terminals with a maximum 10% voltage drop at the RM-1
relay.
Burglary Zone Wiring
Burglary zone definition, (eg. Delay, Instant, 24 Hr. etc.) is
programmed via the keypad. See the Programming Guide,
Section [11].
NC
EOL RESISTOR
LOOPS USING
NO & NC
DEVICES
Wire Gauge Max. Run Length to
AWG
Figures based on maximum loop
24
resistance of 100 ohms.
Max. Wire Run to E.O.L. Relay
AWG
AWG
AWG
AWG
14
16
18
4750'
3000'
1880'
1500'
1447m 914m
573m
457m
2375'
1500'
940'
723m
457m
286m
228m
1190'
750'
470'
362m
228m
143m
112m
790'
500'
310'
240m
152m
94m
595'
375'
235'
181m
114m
71m
Z1
COM Z2
NC
NC
NO
5600Ω 0.5W
5600Ω 0.5W
END OF LINE
END OF LINE
RESISTOR
RESISTOR
Zone Wiring Chart
(AWG)
End-of-Line resistor
24
1900'
(579m)
22
3000'
(914m)
20
4900' (1493m)
19
6200' (1889m)
18
7800' (2377m)
AWG
19
22
750'
228m
750'
370'
112m
370'
180'
56m
250'
120'
76m
36m
185'
90'
56m
27m
EOL RESISTOR
LOOPS USING
NC DEVICES
ONLY
3

Advertisement

Table of Contents
loading

Table of Contents