HOOK-UP DIAGRAM
+
12V 4Ah
SEALED
BATTERY
Battery Charge Current:
360mA Max
Battery capacity for
emergency standby is at
least 4 hours if the total
load (BELL + AUX O/P) is
800mA or less.
Recommended battery is
Yuasa MNP4-12.
16V
AC
40VA minimum
AC POWER
Do not connect transformer to a
receptacle controlled by a
switch.
TO AUX+
TERMINAL
Ready
Armed
Memory
Bypass
Trouble
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
PC1500RK / PC1500RKF
KEYPAD - 5 MAXIMUM
Refer to Installation Manual
text for detailed instructions
on keypad wiring.
Temperature Range: 0˚C-47˚C (32˚F-120˚F)
Maximum Humidity: 85% R.H.
WARNING
For continued protection
against the risk of fire,
replace only with the same
type and rating of fuse.
INCORRECT CONNECTIONS MAY RESULT IN
FUSE FAILURE OR IMPROPER OPERATION.
INSPECT WIRING AND ENSURE CONNECTIONS
ARE CORRECT BEFORE APPLYING POWER.
+
-
+
PGM
AC
AUX
BELL
OUT
SIREN
12V
DC
1A maximum
OBSERVE
POLARITY
LOAD
300 mA MAX
Power 12V
-
YEL GRN Z1
Z2
Z3
KEYPAD
COM
COM
NC
NO
5600Ω 0.5W
END OF LINE
RESISTOR
LOOP USING
NO and NC
DEVICES
To
IN
PGM
-
Smoke
N.O.
IN
Detector
OUT
ALM
DC
+
To
AUX
OUT
+
WHT
Latching 4-wire
smoke detector
(ESL model 445C)
5600Ω 0.5W
END OF LINE
RESISTOR
Z4
Z5
Z6 R-1 T-1 RNG TIP
COM
GRY BRN RED GRN
RJ31-X CORD
NC
RJ31-X
TELEPHONE
PLUG
NC
5600Ω 0.5W
END OF LINE
RESISTOR
LOOP USING
NC DEVICES
ONLY
BLK
WHT
RM-1 Power loop
-
supervisory relay
12VDC 35mA max.
+
RED
GRN
Alarm initiating
loop resistance:
100 ohms
Refer to installation guidelines
when locating smoke detectors.