Toshiba V Series Manual page 98

Integrated, devicenet module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Chapter 4 Operating Procedures for the DN311 (Software)
4
78
(4) Operation mode specifying information: 1 is significant in any of these bits.
F
E
D
C
B
0
0
0
STBY
RUN
Figure 4-17 Bit Configuration of Operation Mode Specifying Information
Table 4-15 Description of Operation Mode Specifying Information Bits
Bit
Name
D
STBY
Standby request: Change from run mode to standby mode
C
RUN
Run request: Change from standby mode to run mode
A
BITS
Bit strobe transmission enable
9
POLL
Polling transmission enable
4
START
1: Polling/bit strobe transmission start
S controller ↔ DN311 transfer mode
3
SYNC
1: Synchronous
(5) Others
• The following combinations of requests are inhibited in operation mode specifying
information
(a) Simultaneous requests of standby and run
(b) Requesting an existing mode (standby/run)
• For confirmation of actual mode changes, refer to station status.
• To change bits A, 9, 4, and 3, set the DN311 in standby mode, then request new
settings together with a run request.
• Standby cannot be requested when bits A, 9, 4, and 3 are set to 1.
A
9
8
7
6
0
0
0
BITS
POLL
Description
0: Asynchronous
model 3000 DeviceNet Module Manual (DN311/DN311A)
5
4
3
2
1
0
0
0
START
SYNC
0: Transmission stop
0
0