Toshiba V Series Manual page 77

Integrated, devicenet module
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

(2) Down Information (05D4H: 1 word)
This register stores data of the cause of the DN311 getting into down mode. When
this happens, the 7-segment LED on the front panel show the following down codes.
Down Code
(hexadecimal)
F0H
F1H
F2H
F3H
F4H
F5H
F6H
F7H
F8H
(3) Polling/bit strobe scan cycle (05CFH to 05D3H: 5 words)
This area stores the DN311's scan time in milliseconds during transmission in polling
mode or bit strobe mode.
Asynchronous mode: The scan cycle means the time from when the DN311 finishes
data input/output with all slave devices until it restarts data input/output next.
Synchronous mode: The scan completion time means the time from when "1" is
written in the bit strobe output data semaphore/polling output data semaphore
until the DN311 writes "1" in the input data semaphore.
05CFH
05D0H
05D1H
05D2H
05D3H
6F8C0903
Table 4-4 Down Information
Watchdog timeout
Memory bus error
TRAP
ROM's BCC check error (at DN311 start)
RAM's read/write error (at DN311 start)
Read/Write error pndtw3 for S controller communication
DN311 node address setting error
DN311 network communication rate setting error
Configuration data EEPROM read error
• If all the slave devices are in polling mode, the scan cycle means the time
from the start of a polling input/output until the restart of another polling input/
output next.
• If all the slave devices are in bit strobe mode, the scan cycle means the time
from the start of a bit strobe input/output until the restart of another bit strobe
input/output next.
• If slave devices of polling mode and bit strobe mode are mixedly used, the
scan cycle means the time from the finish of a polling input/output following
the start of a bit strobe input/output until the restart of another bit strobe input/
output next.
Table 4-5 Scan Cycles
Scan cycle/scan completion time
Asynchronous mode: Minimum scan cycle
Asynchronous mode: Maximum scan cycle
Synchronous mode: Minimum scan completion time
Synchronous mode: Maximum scan completion time
4.2 S Controller Interface Buffer Memory Configuration
Cause of Down Mode
4
(at DN311 start)
57

Advertisement

Table of Contents
loading

This manual is also suitable for:

3000Dn311Dn311a