Technical specifications
Voltages, currents, electrical potentials
Rated electronics supply voltage L +
Reverse polarity protection
Constant measuring current for resistance-type transmitters
Electrical isolation
between channels and the backplane bus
between channels and electronics power supply
between channels
In groups of
Maximum potential difference
between channels (U
Between the channels and M
Isolation test voltage
Current consumption
from the backplane bus
from supply voltage L+
Power loss of the module
Generation of analog values
Measuring principle
Integration/conversion time/resolution (per channel)
programmable
Integration time in ms
Basic conversion time in ms
Additional conversion time for wire-break monitoring
Resolution (including overshoot range)
Interference frequency suppression at interference fre-
quency f1 in Hz
Measured value smoothing
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.11 Analog input module SM 331, AI 6 x TC isolated (6ES7331-7PE10-0AB0)
)
CM
(V
)
internal
iso
(1)
(2)
24 VDC
Yes
Typ. 0.9 mA
Yes
Yes
Yes
1
250 VAC
250 VAC
2,500 VDC
max. 100 mA
max. 150 mA
Typ. 2.2 W
Integrating
Yes
10/16.67/20/100
30/50/60/300
65 ms
15 bits + sign
400/60/50/10
none/weak/medium/strong
Analog modules