Parameters
Table 6- 20
Overview of the parameters for SM 331; AI 8 x 12 Bit
Parameters
Enable
•
Diagnostics interrupt
•
Process interrupt when
limit exceeded
Process interrupt trigger
•
High limit
•
Low limit
Diagnostics
•
Group diagnostics
•
with line continuity check
Measurement
•
Measurement type
•
Measuring range
•
Noise suppression
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0)
Range of values
yes/no
yes/no
May be restricted by the measuring range
from 32511 to - 32512
from - 32512 to 32511
yes/no
yes/no
disabled
Voltage V
4DMU current (4-wire transducer)
2DMU current (2-wire transducer)
R-4L resistance (4-wire connection)
RTD-4L thermoresistor
(linear, 4-wire connection)
TC-I thermocouple
(internal comparison)
TC-E thermocouple
(external comparison)
TC-IL thermocouple
(internal comparison)
TC-EL thermocouple
(linear, external comparison)
Measurement types and rang-
See the table
es
400 Hz; 60 Hz; 50 Hz; 10 Hz
Default
Parameter
type
no
dynamic
no
-
dynamic
no
static
no
V
dynamic
± 10 V
50 Hz
Analog modules
Scope
Module
Channel
Channel
group
Channel or
channel
group
365