Representation of analog values in the current output ranges
Table 5- 39
Representation of analog values in the ±20 mA output range
System
dec
118,5149 %
32767
32512
117,589 %
32511
27649
100 %
27648
75 %
20736
0,003617 %
1
0 %
0
-1
-75 %
-20736
-100 %
-27648
-27649
-117,593 %
-32512
-32513
-118,519 %
-32768
Table 5- 40
Representation of analog values in the 0 mA to 20 mA and 4 mA to 20 mA output ranges
System
dec
118,5149 %
32767
32512
117,589 %
32511
27649
100 %
27648
75 %
20736
0,003617 %
1
0 %
0
-1
-25 %
-6912
-6913
-117,593 %
-32512
-32513
-118,519 %
-32768
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
5.2 Representation of analog values for analog output channels
Current output range
hex
±20 mA
7FFF
0.00 mA
7F00
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
-723.4 nA
AF00
-15 mA
9400
-20 mA
93FF
8100
-23.52 mA
80FF
8000
0.00 mA
Current output range
hex
0 mA to 20 mA
7FFF
0.00 mA
7F00
7EFF
23.52 mA
6C01
6C00
20 mA
5100
15 mA
1
723.4 nA
0
0 mA
FFFF
E500
E4FF
8100
80FF
8000
0.00 mA
Overflow, off power
Overshoot range
Rated range
Undershoot range
Underflow, at zero voltage and current
4 mA to 20 mA
0.00 mA
22.81 mA
20 mA
16 mA
4 mA + 578.7 nA
4 mA
0 mA
0.00 mA
Principles of analog modules
Overflow, off power
Overshoot range
Rated range
Undershoot range
Not supported. Output value
limited to 0 mA.
Underflow, at zero voltage
and current