Siemens SIMATIC Manual page 269

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Table 5- 15
Representation of the analog values of Ni 100, 120, 200, 500, 1000 and
LG-Ni 1000 resistance thermometers
Ni x00 cli-
Units
matic in °C
dec
hex
(1 digit =
0.01 °C)
> 295.00
32767
7FFF
295.00
29500
733C
:
:
:
250.01
25001
61A9
250.00
25000
61A8
:
:
:
-60.00
-6000
E890
-60.01
-6001
E88F
:
:
:
-105.00
-10500
D6FC
< - 105.00
-32768
8000
Representation of the analog values of Ni 100 GOST Standard resistance thermometers
Table 5- 16
Representation of the analog values of Ni 100 GOST Standard resistance thermometers
Ni 100
Units
GOST
dec
hex
Standard
in °C (1
digit =
0.1°C)
> 212.4
32767
7FFF
212.4
2124
084C
:
:
:
180.1
1801
0709
180.0
1800
0708
:
:
:
-60.0
-600
FDA8
-60.1
-601
FDA7
:
:
:
-105.0
-1050
FBE6
< - 105.0
-32768
8000
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Ni x00 cli-
Units
matic in °F
dec
(1 digit =
0.01 °F)
> 327.66
32767
H
327.66
32766
H
:
:
280.01
28001
H
280.00
28000
H
:
:
-76.00
-7600
H
-76.01
-7601
H
:
:
-157.00
-15700
H
< - 157.00
-32768
H
Ni 100
Units
GOST
dec
Standard in
°F (1 digit =
0.1 °F)
> 414.3
32767
H
414.3
4143
H
:
:
356.1
3561
H
356.0
3560
H
:
:
-76.0
-760
H
-76.1
-761
H
:
:
-157.0
-1570
H
< - 157.0
-32768
H
5.1 Representation of the values for analog input channels
Range
hex
7FFF
Overflow
H
7FFE
Overshoot range
H
:
6D61
H
6D60
Rated range
H
:
E250
H
E24F
Undershoot range
H
:
C2AC
H
8000
Underflow
H
Range
hex
7FFF
Overflow
H
102F
Overshoot range
H
:
0DE9
H
0DE8
Rated range
H
:
FD08
H
FD07
Undershoot range
H
:
F9DE
H
8000
Underflow
H
Principles of analog modules
269

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data