Representation of the analog values of thermocouples type J
Table 5- 27
Representation of the analog values of thermocouples type J
Type J
Units
in °C
dec
> 1450.0
32767
1450.0
14500
:
:
1200.1
12001
1200.0
12000
:
:
-210.0
-2100
< -210.0
< -2100
Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong
type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...
... from F31C
underflow and
H
outputs 8000
.
H
Representation of the analog values of thermocouples type K
Table 5- 28
Representation of the analog values of thermocouples type K
Type K
Units
in °C
dec
> 1622.0
32767
1622.0
16220
:
:
1372.1
13721
1372.0
13720
:
:
-270.0
-2700
< -270.0
< -2700
Faulty wiring (polarity reversal, or open inputs, for example), or sensor error in the negative range (wrong
type of thermocouple, for example) will cause the analog input module to signal underflow, starting at ...
... from F0C4
underflow and
H
outputs 8000
.
H
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Type J in °F Units
hex
dec
7FFF
> 2642.0
32767
H
38A4
2642.0
26420
H
:
:
:
2EE1
2192.2
21922
H
2EE0
2192.0
21920
H
:
:
:
F7CC
-346.0
-3460
H
<F7CC
< -346.0
< -3460
H
... from EA0C
H
outputs 8000
.
H
Type K in
°F
hex
7FFF
> 2951.6
H
3F5C
2951.6
H
:
:
3599
2501.8
H
3598
2501.6
H
:
:
F574
-454.0
H
< F574
< -454.0
H
... from E5D4
H
outputs 8000
H
5.1 Representation of the values for analog input channels
Type J in K
hex
7FFF
> 1723.2
H
6734
1723.2
H
:
:
55A2
1473.3
H
55A0
1473.2
H
:
:
F27C
63.2
H
<F27C
< 63.2
H
underflow and
... from FDC8
outputs 8000
Units
Type K in K
dec
hex
32767
7FFF
> 1895.2
H
29516
734C
1895.2
H
:
:
:
25018
61BA
1645.3
H
25061
61B8
1645.2
H
:
:
:
-4540
EE44
0
H
< -4540
<EE44
< 0
H
underflow and
... from FB70
.
outputs 8000
Principles of analog modules
Units
Range
dec
hex
32767
7FFF
Overflow
H
17232
4350
Overshoot
H
range
:
:
14733
398D
H
14732
398C
Rated range
H
:
:
632
0278
H
< 632
< 0278
Underflow
H
underflow and
H
.
H
Units
Range
dec
hex
32767
7FFF
Overflow
H
18952
4A08
Overshoot
H
range
:
:
16453
4045
H
16452
4044
Rated range
H
:
:
0
0000
H
< 0
< 0000
Underflow
H
underflow and
H
.
H
275