Digital modules
3.31 Digital output module SM 322;DO 8 x AC 120/230 V/2 A; (6ES7322-1FF01-0AA0)
Technical specifications
Actuator selection data
Output voltage
"1" signal
At maximum current
At minimum current
Output current
"1" signal
Rated value
permissible range at 0 °C to 40 °C
permissible range at 40 °C to 60 °C
Maximum inrush current (per group)
"0" signal (residual current)
Output delay (resistive load)
"0" to "1" transition
"1" to "0" transition
Minimum load current
Zero transition
Size of the motor starter
Lamp load
Wiring two outputs in parallel
for redundant load control
for performance increase
Control of a digital input
Switching frequency
with resistive load
with inductive load to IEC 947-5-1, AC 15
with lamp load
Short-circuit protection of the output
Fuse-tripping current
Response time
Replacement fuses
Wickman
Schurter
Littlefuse
Fuse holder
Wickman
Wiring of the actuators
1) The load current must not be half-wave
2) Possible errors:
- no load voltage
- defective fuse
190
min. L1 (-1.5 V)
min. L1 (-8.5 V)
AC 2 A
1)
10 mA to 2 A
10 mA to 1 A
max. 20 A (max. 1 AC cycle)
max. 2 mA
max. 1 AC cycle
max. 1 AC cycle
10 mA
max. 60 V
max. size 5 to NEMA
max. 50 W
supported (only outputs of the same group)
not supported
supported
max. 10 Hz
max. 0.5 Hz
max. 1 Hz
Fuse, 8 A/250 V; per group
min. 40 A
max. 300 ms
8 A fuse/fast-blow
194-1800-0
SP001.1013
217.008
653 07
using a 20-pin front connector
Manual, 06/2017, A5E00105505-AJ