Technical specifications
An RC quenching element (jumper "SJ" inserted) or an external protection circuit extend the service life of contacts.
Size of the motor starter
Lamp load (230 V AC)
Energy-saving lamps/fluorescent lamps with electronic ballast
Fluorescent lamps, conventionally compensated
Fluorescent lamps, non-compensated
Contact protection
Wiring two outputs in parallel
•
for redundant load control
•
for performance increase
Control of a digital input
Switching frequency
•
Mechanical
•
with resistive load
•
with inductive load to IEC 947-5-1, DC13/AC15
•
with lamp load
Wiring of the actuators
1)
Without inserted jumper (SJ).
2)
With AC load voltage and inserted jumper (SJ). No residual current if the jumper (SJ) is not installed.
3)
The sum of all inrush currents on a ballast connected to an output must not
exceed 5 A.
Note
The residual current of an RC quenching element connected to IEC Type 1 inputs may
cause unwanted signal states. Remove the SJ jumper to rectify this fault.
Configuration in RUN
Special considerations must be given if you use the Configuration in RUN function.
SF LED is lit:
Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or
module), although diagnostics are no longer pending and the module is operating correctly.
Solution:
● Only change the configuration when no diagnostics are pending for the module or
● Pulling and plugging the module.
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
3.35 Relay output module SM 322; DO 8 x Rel. 230VAC/5A; (6ES7322-5HF00-0AB0)
max. size 5 to NEMA
Power
1000 W
1500 W
3)
10 x 58 W
1 x 58 W
10 x 58 W
RC quenching element; 330 Ω, 0.1 µF
supported (only outputs with the same load voltage)
not supported
supported
max. 10 Hz
max. 2 Hz
max. 0.5 Hz
max. 2 Hz
using a 40-pin front connector
Digital modules
No. of switching cycles
(typical)
25000
10000
25000
25000
25000