Bacnet/Ip; Outline; Initial Setting For Bacnet/Ip - Mitsubishi Electric 800 Series Instruction Manual

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.8

BACnet/IP

2.8.1

Outline

Operation or parameter setting via communication is possible using the BACnet/IP through the Ethernet connector on the
inverter.
 Communication specifications
The specifications conform to the BACnet standard of the Ethernet physical medium.
Physical medium
Supported property of BACnet standard object type
Supported BIBBs (Annex K)
BACnet standardized device profile (Annex L)
Segmentation
Device address binding
NOTE
• This product is classified as a BACnet Application Specific Controller (B-ASC).
2.8.2

Initial setting for BACnet/IP

Use the following parameters to perform required settings for Ethernet communication between the inverter and other devices.
To make communication between other devices and the inverter, perform the initial settings of the inverter parameters to match
the communication specifications of the devices. Data communication cannot be made if the initial settings are not made or if
there is any setting error.
Pr.
1427
Ethernet function selection
*1
1
N630
1428
Ethernet function selection
*1
2
N631
1429
Ethernet function selection
*1
3
N632
1430
Ethernet function selection
*1
4
N633
1432
Ethernet communication
N644
check time interval
68
2. Ethernet Communication
2.8 BACnet/IP
Item
Initial
Name
value
5001
45237
45238
9999
1.5 s
Ethernet (ISO 8802-3)
Refer to
page
73.
Refer to
page
78.
Refer to
page
78.
Not supported
Not supported
Setting range
502, 5000 to 5002,
5006 to 5008, 5010 to
*3
5013, 9999, 34962
,
Set the application, protocol, etc.
*2
44818
, 45237,
*2
45238, 47808
,
61450
Ethernet communication is available, but the inverter output
0
is shut off in the NET operation mode.
Set the interval of the communication check (signal loss
detection) time for all devices with IP addresses in the range
specified for Ethernet command source selection (Pr.1449
0.1 to 999.8 s
to Pr.1454).
If a no-communication state persists for longer than the
permissible time, the inverter output will be shut off.
9999
No communication check (signal loss detection)
Description
Setting range