Bacnet/Ip; Outline; Initial Setting For Bacnet/Ip - Mitsubishi Electric FR-E800 Instruction Manual (Communication

Hide thumbs Also See for FR-E800:
Table of Contents

Advertisement

2.8

BACnet/IP

2.8.1

Outline

BACnet/IP is available only for the FR-E800-EPA and the FR-E800-SCEPA.
Operation or parameter setting via communication is possible using the BACnet/IP through the Ethernet connector on the
inverter.
 Communication specifications
The specifications conform to the BACnet standard of the Ethernet physical medium.
Item
Physical medium
Supported property of BACnet standard object type
Supported BIBBs (Annex K)
BACnet standardized device profile (Annex L)
Segmentation
Device address binding
Topology
NOTE
• This product is classified as a BACnet Application Specific Controller (B-ASC).
2.8.2

Initial setting for BACnet/IP

Use the following parameters to perform required settings for Ethernet communication between the inverter and other devices.
To make communication between other devices and the inverter, perform the initial settings of the inverter parameters to match
the communication specifications of the devices. Data communication cannot be made if the initial settings are not made or if
there is any setting error.
Pr.
Name
1427
Ethernet function selection
*1
1
N630
1428
Ethernet function selection
*1
2
N631
1429
Ethernet function selection
*1
3
N632
1430
Ethernet function selection
*1
4
N633
1432
Ethernet communication
N644
check time interval
Ethernet (ISO 8802-3)
Refer to
page
Refer to
page
Refer to
page
Not supported
Not supported
Line, star, or a combination of line and star
Initial
Setting range
value
5001
502, 5000 to 5002,
45237
5006 to 5008, 5010 to
5013, 9999, 44818,
45237, 45238,
45238
47808, 61450
9999
0
1.5 s
0.1 to 999.8 s
9999
Description
102.
107.
107.
Setting range
Set the application, protocol, etc.
Ethernet communication is available, but the inverter output
is shut off in the NET operation mode.
Set the interval of the communication check (signal loss
detection) time for all devices with IP addresses in the range
specified for Ethernet command source selection (Pr.1449
to Pr.1454).
If a no-communication state persists for longer than the
permissible time, the inverter output will be shut off.
No communication check (signal loss detection)
2. Ethernet Communication
1
2
3
4
5
6
7
8
9
10
97
2.8 BACnet/IP