Mitsubishi Electric 800 Series Instruction Manual page 105

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Service
Class
Get_Attribute_Single
Get_Attributes_All
 Class attribute
No.
1
Revision
 Instance attribute
No.
1
Vendor ID
2
Device Type
3
Product Code
Revision
4
Major revision
Minor revision
5
Status
6
Serial Number
7
Product Name
11
Active language
12
Supported Language List
• Status (Attribute 5)
Bit
0
Module Owned
1
2
Configured
3
4 to 7
Extended Device Status
8
Minor Recoverable Fault
9
Minor Unrecoverable Fault
10
Major Recoverable Fault
11
Major Unrecoverable Fault
12 to 15
 Assembly Object (04h)
The Assembly object uses static assemblies and holds the Process Data sent/received by the inverter. All instances are
predefined for specific drive profile parameters.
104
2. Ethernet Communication
2.11 EtherNet/IP
Instance
Get_Attribute_Single
Set_Attribute_Single
Get_Attributes_All
Reset (inverter reset)
Name
Access
Get
Name
Access
Get
Get
Get
Get
Get
Get
Get
Set
Get
Name
CIP connection established
Fixed to 0
Fixed to 1 (configured)
Fixed to 0
0000b: Unkown
0010b: Faulted I/O Connection (ExclusiveOwner connection timed out)
0011b: No I/O connection establish (I/O connection not established)
0100b: Non volatile configuration bad
0101b: Major fault (Bit 10 = 1)
0110b: Connection in Run mode (I/O connection established, with Run mode
connection)
0111b: Connection in Idle mode (I/O connection established)
Warning or alarm
Fixed to 0
Fault
Fixed to 0
Fixed to 0
Type
UINT
0001h (Revision of the object)
Type
UINT
00A1h (Mitsubishi Electric)
UINT
0002h (AC Drive)
UINT
003Eh (Product code)
Structure
Major revision and minor revision
USINT
0001h (Major revision number)
USINT
0001h (Minor revision number)
WORD
Refer to "Status (Attribute 5)" on
UDINT
Serial number of the inverter
SHORT_
FR-E800-E (Product name)
STRING
Structure
Active language
USINT
USINT
e, n, g (English)
USINT
Structure
List of languages supported by the host application
array
USINT
USINT
e, n, g (English)
USINT
Description
Description
Description
page
104.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e800

Table of Contents