Variable
Address
type
C3 (83)
0007
C3 (83)
0008
C3 (83)
000A
C3 (83)
000B
C3 (83)
000C
C3 (83)
000D
C3 (83)
000E
C3 (83)
000F
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Parameter
name
PID ON/OFF
H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
Standard or
H'00000000 (0): Standard
Heating/Cooling
H'00000001 (1): Heating and cooling
Control Period
H'FFFFFFFE (−2): 0.1 s
(Heating)
H'FFFFFFFF (−1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Control Period
H'FFFFFFFE (−2): 0.1 s
(Cooling)
H'FFFFFFFF (−1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Direct/Reverse
H'00000000 (0): Reverse operation
Operation
H'00000001 (1): Direct operation
Alarm 1 Type
H'00000000 (0):
H'00000001 (1):
H'00000002 (2):
H'00000003 (3):
H'00000004 (4):
H'00000005 (5):
H'00000006 (6):
H'00000007 (7):
H'00000008 (8):
H'00000009 (9):
H'0000000A (10): Absolute-value upper-limit alarm with
H'0000000B (11): Absolute-value lower-limit alarm with
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): SP absolute-value upper-limit alarm
H'0000000F (15):
H'00000010 (16):
H'00000011 (17):
Alarm 2 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However, the
LBA (loop burnout alarm) cannot be set.
Alarm 3 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However, the
LBA (loop burnout alarm) cannot be set.
3 Communications Data for CompoWay/F
Setting (monitor) value
Alarm function OFF
Upper and lower-limit alarm
Upper-limit alarm
Lower-limit alarm
Upper and lower-limit range alarm
Upper and lower-limit alarm with
standby sequence
Upper-limit alarm with standby
sequence
Lower-limit alarm with standby
sequence
Absolute-value upper-limit alarm
Absolute-value lower-limit alarm
standby sequence
standby sequence
SP absolute-value lower-limit alarm
MV absolute-value upper-limit alarm
MV absolute-value lower-limit alarm
Level
Initial
setting
3
3 - 9