Omron E5C-T Series Communications Manual page 55

Digital temperature controllers programmable type
Table of Contents

Advertisement

Variable
Address
type
C3 (83)
0007
C3 (83)
0008
C3 (83)
000A
C3 (83)
000B
C3 (83)
000C
C3 (83)
000D
C3 (83)
000E
C3 (83)
000F
E5C-T Digital Temperature Controllers Programmable Type Communications Manual (H186)
Parameter
name
PID ON/OFF
H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
Standard or
H'00000000 (0): Standard
Heating/Cooling
H'00000001 (1): Heating and cooling
Control Period
H'FFFFFFFE (−2): 0.1 s
(Heating)
H'FFFFFFFF (−1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Control Period
H'FFFFFFFE (−2): 0.1 s
(Cooling)
H'FFFFFFFF (−1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Direct/Reverse
H'00000000 (0): Reverse operation
Operation
H'00000001 (1): Direct operation
Alarm 1 Type
H'00000000 (0):
H'00000001 (1):
H'00000002 (2):
H'00000003 (3):
H'00000004 (4):
H'00000005 (5):
H'00000006 (6):
H'00000007 (7):
H'00000008 (8):
H'00000009 (9):
H'0000000A (10): Absolute-value upper-limit alarm with
H'0000000B (11): Absolute-value lower-limit alarm with
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): SP absolute-value upper-limit alarm
H'0000000F (15):
H'00000010 (16):
H'00000011 (17):
Alarm 2 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However, the
LBA (loop burnout alarm) cannot be set.
Alarm 3 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type. However, the
LBA (loop burnout alarm) cannot be set.
3 Communications Data for CompoWay/F
Setting (monitor) value
Alarm function OFF
Upper and lower-limit alarm
Upper-limit alarm
Lower-limit alarm
Upper and lower-limit range alarm
Upper and lower-limit alarm with
standby sequence
Upper-limit alarm with standby
sequence
Lower-limit alarm with standby
sequence
Absolute-value upper-limit alarm
Absolute-value lower-limit alarm
standby sequence
standby sequence
SP absolute-value lower-limit alarm
MV absolute-value upper-limit alarm
MV absolute-value lower-limit alarm
Level
Initial
setting
3
3 - 9