Operating Instructions
RIA45
Panel meter
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser RIA45

  • Page 1 Products Solutions Services BA00272R/09/EN/05.15 71300679 Valid as of FW version 01.03.xx (Gerätesoftware) Operating Instructions RIA45 Panel meter...
  • Page 3: Table Of Contents

    RIA45 Table of contents Table of contents Document information ....4 Troubleshooting ....40 Document function .
  • Page 4: Document Information

    Document information RIA45 Document information Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
  • Page 5 RIA45 Document information 1.2.3 Symbols for certain types of information Symbol Meaning Permitted Procedures, processes or actions that are permitted. Preferred Procedures, processes or actions that are preferred. Forbidden Procedures, processes or actions that are forbidden. Indicates additional information. Reference to documentation...
  • Page 6: Safety Instructions

    Conversions to the device Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers. ‣ If, despite this, modifications are required, consult with Endress+Hauser. Repair To ensure continued operational safety and reliability, ‣ Carry out repairs on the device only if they are expressly permitted.
  • Page 7: Product Safety

    If a plastic transmitter housing is permanently exposed to certain steam and air mixtures, this can damage the housing. ‣ If you are unsure, please contact your Endress+Hauser Sales Center for clarification. ‣ If used in an approval-related area, observe the information on the nameplate.
  • Page 8: Identification

    Identification RIA45 Identification Device designation 3.1.1 Nameplate Compare the nameplate on the device with the following diagram: A0010405  1 Nameplate of the device (sample) Order code, serial number and ID number of the device Power supply Power consumption Approval...
  • Page 9: Installation

    RIA45 Installation Installation Incoming acceptance, transport, storage The permitted ambient and storage conditions must be observed. The precise specifications can be found in Section "Technical data". 4.1.1 Incoming acceptance On receipt of the goods, check the following points: • Are the packaging or contents damaged? •...
  • Page 10: Installation Procedure

    Installation RIA45 Installation procedure The panel cutout required measures 92 mm (3.62 in) x 45 mm (1.77 in) A0010404  2 Installation in the panel 1. Screw the threaded rods (pos. 1) into the positions provided on the mounting frame (pos.
  • Page 11: Wiring

    RIA45 Wiring Wiring WARNING Danger! Electric voltage! ‣ The entire connection of the device must take place while the device is de-energized. ‣ The ground connection must be made before all other connections. Danger if protective ground is disconnected. ‣...
  • Page 12 Wiring RIA45 5.1.1 Overview of possible connection options at the device Terminal assignment of analog inputs, channel 1 and 2 (optional) 15 16 17 18 25 26 27 28 A0010406 Connection of the loop power supply 2-Leiter 4-Leiter LPS 2-W...
  • Page 13: Post-Connection Check

    RIA45 Wiring Connection of the analog output Analog output 1 Analog output 2 (optional) O15 O16 O25O26 A0010416 A0010414 Connection of the digital output Digital output/open collector D11D12 A0010415 Connection of the power supply 24 to 230 V AC/DC (-20 % / +10 %) 50/60 Hz...
  • Page 14: Operation

    1. Firstly, install the device driver "CDI DTMlibrary" in FieldCare. It can be found under "Endress+Hauser Device DTMs → Service / Specific → CDI" in FieldCare. 2. Then the DTM catalog must be updated. Add the new installed DTMs to the DTM catalog.
  • Page 15 RIA45 Operation Installing the Windows driver for the TXU10/FXA291 To install the Windows driver Administrator rights are required. Proceed as follows: 1. Connect the device to the PC using the TXU10/FXA291 interface adapter.  A new device is detected and the Windows installation assistant opens.
  • Page 16: Display And Device Status Indicator/Led

    Operation RIA45 Display and device status indicator/LED The device provides an illuminated LC display which is split into two sections. The segment section displays the value of the channel and additional information and alarms. In the dot matrix section, additional channel information, such as the TAG, unit or bar graph, is displayed in the display mode.
  • Page 17: Quick Guide To The Operating Matrix

    RIA45 Operation Underrange/overrange: In the dot matrix section, the error and channel name (TAG) are specified. 6.3.2 Icons in the editing mode The following characters can be used to enter user-defined text: ‘0-9’, ‘a-z’, ‘A-Z’, ‘+’, ‘-’, ‘*’, ‘/’, ‘\’, ‘%’, ‘°’, ‘2’, ‘3’, ‘m’, ‘.’, ‘,’, ‘;’, ‘:’, ‘!’, ‘?’, ‘_’, ‘#’, ‘$’, ‘"’, ‘´’, ‘(’, ‘)’, ‘~’...
  • Page 18 Operation RIA45 Setup menu Description  Application Application selection 1-channel 1-channel application 2-channel 2-channel application Diff-pressure Difference pressure application  AI1 Lower range* Lower measuring range limit for Analog in 1  AI1 Upper range* Upper measuring range limit for Analog in 1 ...
  • Page 19 RIA45 Operation Setup menu Description Reset min/max Reset min/max values Calc value 2 Calculated value 2 See Calc value 1  Analog out 1 Analog output 1 Assignment Assignment for analog output Signal type Signal type of analog output Lower range...
  • Page 20 Operation RIA45 Expert menu Description Bar 100% Upper limit for bargraph of analog input Decimal places Decimal place for analog input Damping Damping Failure mode Failure mode Fixed fail value Fixed value in the event of an error (only, if Failure mode =...
  • Page 21: Commissioning

    RIA45 Commissioning Commissioning Post-installation check and switching on the device Make sure that all post-connection checks have been carried out before you commission your device: • ‘Post-installation check’ checklist →  10 • ‘Post-connection check’ checklist →  13 Once the operating voltage is applied, the display lights up and the green LED indicates that the device is operational.
  • Page 22: Configuring The Device

    Commissioning RIA45 9. Confirm the last position of the code to exit the menu. The code is displayed in full. Press + to scroll to the last point of the submenu x Back and confirm this point. As a result, the value is accepted and the user returns to the level of the Setup menu. Also exit this submenu via the last x Back parameter to get back to the measured value/ channel display.
  • Page 23 RIA45 Commissioning Differential pressure application A concise setup is available for differential pressure applications. Once the differential pressure application setup has been successfully completed, the configured parameters of the analog inputs and the linearization points are used to automatically form the difference between the two inputs and linearize the signal. As a result, the volume is already shown on the display (= calculated value 2).
  • Page 24 Commissioning RIA45 ‘Setup’ menu item Setup → Application → ‘Diff pressure’ Preconfigured by application package Submenu Setup analog inputs AI1 Lower range: start of measuring range, analog input 1 Signal: Current (corresponds to 4 mA for example) Range: 4-20 mA AI1 Upper range: end of measuring range, analog input 1 →...
  • Page 25 RIA45 Commissioning Current Voltage RTD (resistance TC (thermocouple) Off (Deactivate the thermometer) input) Signal range Signal range (see Technical data); start and end of measuring range defined by type selected Lower range Connection (only Start of measuring range; also enter...
  • Page 26 Commissioning RIA45 7.4.4 Step 4: Configuring the analog output(s) The device is fitted with an analog output (optionally with two analog outputs). These outputs can be freely assigned to the inputs and channels available in the device. Setup Analog out 1...
  • Page 27 RIA45 Commissioning Time base: Enter the time base in seconds. Only for operating Time base of gradient calculation mode Gradient. Hysteresis: The hysteresis is configured as an absolute value (only Hysteresis. The switch point can be controlled by positive values) in the unit of the channel in question means of a hysteresis for every limit value.
  • Page 28 Commissioning RIA45 Measured value Setpoint Hysteresis Threshold “off” Setpoint “on” Setpoint “off” A0010187-EN  7 Max operating mode Gradient The "Gradient" operating mode is used to monitor the change in the input signal over time. The alarm is triggered if the measured value reaches or overshoots the set value. If the user configures a positive value, the limit value is monitored for rising gradients.
  • Page 29 RIA45 Commissioning Measured value Hysteresis Setpoint Setpoint Hysteresis Setpoint active Setpoint not active A0010189-EN  9 Outband operating mode InBand The limit value is violated as soon as the measured value to be checked drops below or exceeds a minimum or maximum value specified beforehand. The hysteresis is located at the insides of the band.
  • Page 30 Commissioning RIA45 Measured Delay Delay value Setpoint Hysteresis Delay time is reset Setpoint active Setpoint not active A0010193-EN  11 Hysteresis and delay active 7.4.6 Step 6: Advanced device configuration (access protection/ operating code, saving the current setup) Access protection The access protection locks all the editable parameters, i.e.
  • Page 31 RIA45 Commissioning 7.4.7 Step 7: Configuring the display functions The display is split into a 7-segment display section and a color section. The dot matrix section can be configured separately for each channel. All the active channels (analog inputs and calculated values) are offered for selection.
  • Page 32 Commissioning RIA45 The set limit values for overfill protection must be protected against unintentional modification. The following function must be activated if additional access protection should be provided for the configuration software: Select Setup / Expert → System → Overfill protect: German WHG.
  • Page 33 RIA45 Commissioning The damping is specified in seconds (can be configured in steps of 0.1 s, max. 999.9 s). Default values Input type Default value Current and voltage inputs 0.0 s Temperature inputs 1.0 s Once 5 times the filter time have elapsed, 99% of the actual measured value is reached.
  • Page 34 Commissioning RIA45 Output → Analog output 1/2 Failure mode • Min = Stored minimum value: The stored minimum value is output. • Max = Stored maximum value: The stored maximum value is output. • Fixed value = Constant value: A constant value for output in the event of an error can be entered.
  • Page 35: In Operation

    RIA45 Commissioning Expert → Diagnostics → Simulation: • Select the output to be simulated with the simulation value • Select the relay to be simulated with the status In operation 7.5.1 ‘+’ and ‘-’ quick pick keys You can use the ‘+’ and ‘-’ quick pick keys to switch through all the active channels (universal inputs and calculated values) in the display mode.
  • Page 36 Commissioning RIA45 Troubleshooting instructions and a list of all the error messages can be found in Section Troubleshooting →  40. Measuring range limits Display Display - - - - - - - - - - Measured value - - - - -...
  • Page 37 RIA45 Commissioning List of error codes, see Troubleshooting →  40. Under certain conditions events saved over the past 30 minutes might be lost. 7.5.5 Operating hours counter The device has an internal operating hours counter which also acts as the reference for diagnostic events.
  • Page 38: Maintenance

    Maintenance RIA45 Maintenance No special maintenance work is required on the device. Endress+Hauser...
  • Page 39: Accessories

    Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
  • Page 40: Troubleshooting

    Troubleshooting RIA45 Troubleshooting The following section provides you with an overview of possible causes of errors to provide you with an initial troubleshooting aid. NOTICE Device malfunction possible when retrofitting with untested hardware ‣ When upgrading/retrofitting the device with additional hardware at a later date (relay, additional universal input and additional analog output), an internal hardware test must be performed by the device software.
  • Page 41: Spare Parts

    RIA45 Troubleshooting Error code Meaning Remedy C482 Info: simulation mode, relay/open collector Only for information, device properly working. C483 Info: analog output simulation mode Only for information, device properly working. C561 Display overflow Only for information, device properly working. 10.3 Spare parts Order codes for spare parts can be found on www.endress.com/deviceviewer →...
  • Page 42 Troubleshooting RIA45 Item no. Designation Terminals 4-pin for analog input Terminal, analog input non-Ex (terminals x1, x2, x3, x4 and x5, x6, x7, x8) Terminal, analog input Ex, blue at top (terminals x1, x2, x3, x4) Terminal, analog input Ex, blue at bottom (terminals x5, x6, x7, x8)
  • Page 43: Return

    The measuring device must be returned if it is need of repair or a factory calibration, or if the wrong measuring device has been delivered or ordered. Legal specifications require Endress+Hauser, as an ISO-certified company, to follow certain procedures when handling products that are in contact with the medium.
  • Page 44: Disposal

    Disposal RIA45 Disposal The device contains electronic components and must therefore be disposed of as electronic waste. Comply with local disposal regulations. Endress+Hauser...
  • Page 45: Technical Data

    RIA45 Technical data Technical data 13.1 Input 13.1.1 Inputs One or two universal inputs 13.1.2 Measured variable Current, voltage, resistance, resistance thermometer, thermocouples 13.1.3 Measuring ranges Current: • 0/4 to 20 mA +10% overrange • Short-circuit current: max. 150 mA •...
  • Page 46: Output

    Technical data RIA45 13.2 Output 13.2.1 Output signal One or two analog outputs, galvanically isolated 13.2.2 Current/voltage output Current output: • 0/4 to 20 mA • Overrange up to 22 mA Voltage: • 0 to 10 V, 2 to 10 V, 0 to 5 V, 1 to 5 V •...
  • Page 47: Power Supply

    RIA45 Technical data 13.3 Power supply 13.3.1 Electrical connection LPS 4-W LPS 2-W 0/4...20mA 4...20mA 0/4...20mA U<=1V U>1V 25 26 27 28 0...10V 0/1...5V ±10V Typ J,K,T,N... ±100mV...±1V ±30V R12 R11 R13 R22 R21 R23 Analog Out 15 16 17 18 4...20mA...
  • Page 48: Performance Characteristics

    Technical data RIA45 13.4 Performance characteristics 13.4.1 Reference operating conditions Power supply: 230 V , 50/60 Hz Ambient temperature: 25 °C (77 °F) ± 5 °C (9 °F) Humidity: 20 %...60 % rel. humidity 13.4.2 Maximum measured error Universal input:...
  • Page 49: Installation

    RIA45 Technical data Accuracy Input: Range: Maximum measured error of measuring range (oMR): Typ C (W5Re/W26Re), 0 to 2 320 °C (32 to 4 208 °F) ± (0.15% oMR +1.5 K (2.7 °F)) (ASTME998) from 500 °C (932 °F) Typ B (Pt30Rh-Pt6Rh), 0 to 1 820 °C (32 to 3 308 °F) ±...
  • Page 50 Technical data RIA45 13.5.2 Environment Ambient temperature range NOTICE The life-time of the display is shortened when operated in the upper temperature range. ‣ To avoid heat accumulation, always make sure the device is sufficiently cooled. Non-Ex/Ex devices: –20 to 60 °C (–4 to 140 °F) UL devices: –20 to 50 °C (–4 to 122 °F)
  • Page 51: Mechanical Construction

    RIA45 Technical data 13.6 Mechanical construction 13.6.1 Design, dimensions 118.6 (4.67) 16.7 96 (3.78) (0.66) 151.8 (5.98) 175 (6.89) A0010208  15 Dimensions of the panel meter in mm (in) Distance piece for terminals (Ex option) 13.6.2 Weight Approximately 300 g (10.6 oz) 13.6.3...
  • Page 52: Operability

    Technical data RIA45 13.7 Operability 13.7.1 Display elements A0010223  16 Display of the panel meter Channel display: 1: analog input 1; 2: analog input 2; 1M: calculated value 1; 2M: calculated value 2 Dot matrix display for TAG, bar graph and unit Limit value indicators in the bar graph "Operation locked"...
  • Page 53: Certificates And Approvals

    13.8 Certificates and approvals 13.8.1 CE mark The device meets the legal requirements of the EU directives. Endress+Hauser confirms that the device has been tested successfully by affixing the CE mark. 13.8.2 Ex approval Information about currently available Ex versions (ATEX, FM, CSA, etc.) can be supplied by your E+H Sales Center on request.
  • Page 54: Appendix

    Appendix RIA45 Appendix The following tables show all the parameters available in the configuration menu. The values configured at the factory are marked in bold. 14.1 Further explanations on the differential pressure application at level measurement At both universal inputs pressure sensors are connected. With the following calculation steps the volume in the CV channels is finally calculated: 14.1.1...
  • Page 55 RIA45 Appendix • 1 bar = 0,1 N/mm² = 10 N/m² = 10 • 1 mbar = 1 hPa = 100 Pa Conversion factors for various pressure engineering units Pascal Technical Physical Torr Pounds per Atmosphere Atmosphere square inch [Pa]...
  • Page 56: Display Menu

    Appendix RIA45 Medium Density in [kg/m³] Disulfide Diethyl ether 14.1.2 Calculation step: Calculation of the volume out of the height By means of the linearization of the calculated height value the volume can be calculated. This is done by assigning a certain volume value to every height value in dependency of the tank shape.
  • Page 57: Setup Menu

    RIA45 Appendix Calc value 1/2 Navigation  Display → Calc value 1/Calc value 1 Description Configures the display for math 1 or math 2. If the parameter is set to ‘Off’, the channel is not displayed. Options Unit Bargraph Bar + unit...
  • Page 58 Appendix RIA45 AI1/AI2 Lower range Navigation  Setup → AI1 Lower range/AI2 Lower range Description Configures the measuring range lower limit User entry Numerical value Factory setting 0.0000 Additional information Only visible if → Diff pressure is configured as the application.
  • Page 59 RIA45 Appendix Factory setting 100.00 Additional information Only visible if → Diff pressure is configured as the application. Submenu "Linearization" Navigation  Setup → Linearization Description Only visible if → Diff pressure is configured as the application. No lin points Navigation ...
  • Page 60 Appendix RIA45 Signal range Navigation  Setup → Analog in 1/Analog in 2 → Signal range Description Configures the input signal. Which options are available for selection depends on the "Signal type" set. Options 4-20mA, 4-20mA squar, 0-20mA, 0-20mA squar...
  • Page 61 RIA45 Appendix Unit Navigation  Setup → Analog in 1/Analog in 2 → Unit Description Unit of the channel Input Customized text, max. 5 digits Additional information Only displayed if "Signal type" = "Current" or "Voltage" is set. Temperature unit Navigation ...
  • Page 62 Appendix RIA45 Description Resets the min./max. values saved. Options Factory setting Submenu "Calc value 1"/"Calc value 2" Navigation  Setup → Calc value 1/Calc value 2 Additional information Settings for math 1 or math 2 Calculation Navigation  Setup → Calc value 1/Calc value 2 → Calculation Description Selects the calculation method.
  • Page 63 RIA45 Appendix Description Configures the 100%-value for the bar graph User entry Numerical value Factory setting Factor Navigation  Setup → Calc value 1/Calc value 2 → Factor Description Setting of factor for calculated value User entry Numerical value Factory setting...
  • Page 64 Appendix RIA45 Description Resets the min./max. values saved. Options Factory setting Submenu "Analog Out 1"/"Analog Out 2" Navigation  Setup → Analog Out 1/Analog Out 2 Additional information Settings for analog output 1 or analog output 2 Assignment Navigation  Setup → Analog Out 1/Analog Out 2 → Assignment...
  • Page 65 RIA45 Appendix Submenu "Relay 1"/"Relay 2" Navigation  Setup → Relay 1/Relay 2 Additional information Settings for relay 1 or relay 2 Source Navigation  Setup → Relay 1/Relay 2 → Source Description Selects the source for the relay Options...
  • Page 66: Diagnostics Menu

    Appendix RIA45 Description Time base for gradient calculation in seconds User entry 0-60 Factory setting Additional information Only visible if "Function" = "Gradient" was set Hysteresis Navigation  Setup → Relay 1/Relay 2 → Hysteresis Description Hysteresis for switching threshold(s)
  • Page 67 RIA45 Appendix Navigation  Diagnostics → Current diagn Description Displays the error code currently present Last diagn Navigation  Diagnostics → Last diagn Description Displays the last error code Operating time Navigation  Diagnostics → Operating time Description Displays the hours operated up until now Submenu "Diagnost logbook"...
  • Page 68: Expert Menu

    Appendix RIA45 Order identifier Navigation  Diagnostics → Device information → Order identifier Description Displays the order number Firmware version Navigation  Diagnostics → Device information → Firmware version Description Displays the firmware version ENP Version Navigation  Diagnostics → Device information → ENP Version...
  • Page 69 RIA45 Appendix Submenu "Analog in 1"/"Analog in 2" Navigation  Expert → Input → Analog in 1/Analog in 2 Description Settings for the analog inputs. Additional information The following parameters are available for analog input 1 and analog input Bar 0% Navigation ...
  • Page 70 Appendix RIA45 Description Configures the failsafe mode. Options Invalid Fixed value Factory settings Invalid Additional information Invalid: an invalid value is output in the event of an error. Fixed value: a fixed value is output in the event of an error.
  • Page 71 RIA45 Appendix Description Setting as to whether saved min./ max. values can be reset in the Display menu without having to enter a user code which may already have been configured. Options Factory setting Submenu "Output" Navigation  Expert → Output Submenu "Analog Out 1"/"Analog Out 2"...
  • Page 72 Appendix RIA45 Description Delay for switching the relay. User entry 0-9999 Factory setting Operating mode Navigation  Expert → Output → Relay 1/Relay 2 → Operating mode Description Normally closed = breaker contact Normally opened = maker contact Options normally closed...
  • Page 73 RIA45 Appendix Description Configures the failsafe mode Options Invalid Fixed value Factory setting Invalid Fixed fail value Navigation  Expert → Application → Calc value 1/Calc value 2 → Fixed fail value Description The value configured here is output in the event of an error.
  • Page 74 Appendix RIA45 Description Simulation of analog output 1 or analog output 2. The value configured in the simulation is output at analog output 1 or analog output 2. Options 3.6mA 10mA 12mA 20mA 21mA Factory setting Simu relay 1/2 Navigation ...
  • Page 75: Index

    RIA45 Index Index Access protection ......30 Local operation ......14 Application conditions Configuration .
  • Page 76 Index RIA45 Namur NE 43 ......70 Spare parts ....... . 41 No lin points .