1. Introduction
1.4. About the transmitter
The XYR 6000 Pressure DP model type is capable of measuring mass flow and volumetric flow. When
minimum and maximum flow rate values are configured as PV scale 0% and 100% values at given PV
units of measure, and the respective DP values at those limits are configured as the calibration scale 0%
and 100% values, the PV value becomes a flow rate in the selected units of measure. Minimum and
maximum flow rate data at given DP values is either provided on or with orifice plates, or is commonly
available according to orifice plate size.
DP or AP
Sensor
SP
Pressure
Sensor
Input
Temp
Sensor
2
OneWireless XYR 6000 ISA100.11a Compliant Pressure Transmitter User's Manual
Factory
Characterization
Data
EEPROM
Multi-
A/D
plexer
Meter Body
Figure 1-1 XYR 6000 Functional Diagram
Measurement
Board
Micro-
processor
EEPROM
Electronics Housing
Configuration
Data
Configuration
Data
Radio
Board
EEPROM
Micro-
processor
Battery
Revision 3
March 2012
Antenna