Heating Delta Stage 2 ON
Sets the delta from setpoint that stage 2 heating starts.
Heating Delta Stage 2 OFF
Sets the delta from setpoint that stage 2 heating stops. Stage 2 turns off at setpoint + Delta Stage 2.
Heating Delta Stage 3 ON
Sets the delta from setpoint that stage 3 heating starts.
Heating Delta Stage 3 OFF
Sets the delta from setpoint that stage 1 heating stops. Stage 3 turns off at setpoint + Delta Stage 3.
Cooling Delta Stage 1 ON
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Delta Stage 1 OFF
Sets the delta from setpoint that stage 1 Cooling stops. Stage 1 turns off at setpoint - Delta Stage 1.
Cooling Delta Stage 2 ON
Sets the delta from setpoint that stage 2 cooling starts. Stage 2 turns off at setpoint.
Cooling Delta Stage 2 OFF
Sets the delta from setpoint that stage 2 Cooling stops. Stage 2 turns off at setpoint - Delta Stage 1.
Max Heat SP
Sets the maximum heating setpoint value. Will not ramp or accept setpoints higher that this maximum.
Min Cool SP
Sets the minimum cooling setpoint value. Will not ramp or accept setpoints lower than this minimum.
Minimum Run Time (MRT)
Sets the minimum run time before a heating/cooling cycle can turn off.
Sets heating/cooling cycle time. Prevents rapid cycling.
Thermostat screen will display "Cool ON" or "Heat ON" while the minimum run time is being enforced.
Minimum Off Time (MOT)
Sets the minimum off time before another heating/cooling cycle can begin. Provides compressor short cycle protection.
Thermostat screen will display "WAIT".
Fan Cycler Submenu
The fan cycler function cycles the HVAC system fan for an ON period followed by an Off period continuously. Used to
provide minimum air ventilation requirements. When the Fan ON time is set to a value greater than 0, an additional
"Cycler" FAN mode is present when pressing the FAN button.
Fan ON Time
Fan OFF Time
Range: 1 to 8 degrees
Range: 0 to 8 degrees
Range: 1 to 8 degrees
Range: 0 to 8 degrees
Range: 1 to 8 degrees
Range: 0 to 8 degrees
Range: 1 to 8 degrees
Range: 0 to 8 degrees
Range: 55F to 90F (12C-32C)
Range: 60F to 99F (15C-37C)
Range: 1- 9 Minutes
Range: 5-9 Minutes
Range: 0-120 minutes
Range: 10-120 minutes
Installer Settings Menu (Hidden Screen)
Default: 0
Default: 3
Default: 0
Default: 1
Default: 0
Default: 2
Default: 0
Default: 90F (32C)
Default: 60F (15C)
Default: 3
Default: 5
Default: 0 (=OFF)
Default: 10
Default: 2