Troubleshooting Section
Miscellaneous
Monitoring Mode Shutdowns
"Monitoring Mode Shutdowns" controls the shutdown
feature that is associated with the engine monitoring
feature. When this feature is enabled and an event
code with a "-3" suffix is detected, the engine will be
shut down.
Table 21
Value
Disabled
Enabled
J1939 Continuous Fault Handling
Remote Torque Speed Control Enable
Status
The "Remote Torque Speed Control Enable Status"
parameter determines the way that faults will be
handled by the ECM when the "J1939 Torque Speed
Control (TSC1)" message is used as a speed request
input to the ECM. Programming the "Remote Torque
Speed Control Enable Status" to "Enabled" will cause
the ECM to display a fault code if a valid TSC1
message is not received by the engine ECM within
30 seconds of the engine starting. If the" Remote
Torque Speed Control Enable Status" is programmed
to "Disabled", the engine will display a 247-12 Data
Link malfunction immediately after a loss of a TSC1
message. Program "Remote Torque Speed Control
Enable Status" to "Enabled" if the ECM will always be
receiving a TSC1 message.
Table 22
Value
Disabled
Enabled
Configurable Inputs
Overspeed Protection
The "Overspeed Protection" speed is the engine rpm
when a shutdown will occur. Overspeed protection
is used in order to protect the engine from damage.
Overspeed protection must be enabled in "Monitoring
Mode Shudowns".
Table 23
Minimum
1500 rpm
This document is printed from SPI². Not for RESALE
Default
Disabled
Default
Disabled
Maximum
Default
2100 rpm
2100 rpm
Configurable Governor Droop
"Configurable Governor Droop" allows the engine to
run in "droop mode" when the genset is operated in
parallel with other gensets.
Table 24
Minimum
Maximum
0 percent
8 percent
Coolant Level Sensor
A coolant level sensor is an optional switch input.
Programming the "Coolant Level Sensor" parameter
to "Enabled" notifies the ECM that a coolant level
sensor input is present on pin J1:38. If this parameter
is programmed to "Enabled" and the coolant level
falls below the measured level, a "E2143-3" event
code will be displayed.
Table 25
Value
Disabled
Enabled
Air Filter Restriction Switch Installation
Status
An "Air Filter Restriction Switch" is an optional
switch input. Programming the "Air Filter Restriction
Switch Installation Status" parameter to "Enabled"
notifies the ECM that an input from the air filter
restriction switch is present on pin J1:47. When this
parameter is programmed to "Enabled" and the air
filter restriction switch closes, an E172-1 or J107-15
event code will be displayed.
Table 26
Value
Disabled
Enabled
Fuel/Water Separator Switch Installation
Status
A fuel/water separator switch is an optional switch
input. Programming the "Fuel/Water Separator
Switch Installation Status" parameter to "Enabled"
notifies the ECM that a fuel/water separator switch
input is present on pin J1:44. When this parameter
is programmed to "Enabled" and the fuel/water
separator switch closes, an E232-1 or J97-15 event
code will be displayed.
KENR6201-01
Default
0 percent
Default
Disabled
Default
Disabled