Scaling

To scale the pressure transducer:
Plug the transducer into a fitting with a gauge to read pressure.
Put the highest value of air pressure (500psi maximum) on the fitting.
Enter the pressure reading from the gauge in the High (PSI) field.
Press the Set High Pressure Scale Factor button.
Remove the air pressure, verify the gauge reads zero.
Enter the value (zero) reading from the gauge in the Low (PSI) field.
Press the Set Low Pressure Scale Factor button.
Run the air pressure up and down and verify the gauge reading matches the reading in the Scaled field.
Repeat if necessary.
334116D