Fan Kit; Fan Removal Instructions - Vermont Castings RHEDV25 Installation Instructions & Homeowner's Manual

Direct vent insert
Table of Contents

Advertisement

Vermont Castings, Majestic Products RHEDV Direct Vent Insert
1/2" Gas Supply
1/2" x 3/8" Reducer
3/8" Nipple
FP1278
Fig. 1 Typical gas supply installation.
Always check for gas leaks with a mild
soap and water solution. Do not use an
open flame for leak testing.
Brass
Thermostat
Plug
Bulb
Gas Inlet
Thermocouple Inlet
Pilot Tube Entry
Pilot Adjustment
Screw
Minimum Rate Screw
(Nonadjustable)
Fig. 2 On fireplaces equipped with the Eurosit 630 gas valve,
there are brass plugs in two of the holes. These plugs are not
to be removed. The gas inlet hole has a plastic cap in it.
Remove the plastic cap and connect your gas supply line at
this point.

Fan Kit

115 volt, 60 Hz. 56W
The fan kit includes the following: fan, temperature
sensor, speed control and a 6 ft. cord. The following
explains how to start and set the fan for automatic
operation.
1. Plug in the electrical cord.
2. Start gas fire - see lighting procedures.
3. Turn on fan speed control.
4. Wait until the unit has warmed up sufficiently to
activate the termperature sensor, approx. 5-10
minutes.
6
3/8" x 3/8" Shut Off Valve
3/8" Union
Manifold Gas
Outlet
Brass Plug
Pressure
Regulator
Control
Knob
Control Knob
it
HV118
5. Once fan starts, adjust speed control to desired fan
speed. The fan will now automatically come on every
time the fireplace is in operation. Should the fan not
be needed simply turn off the speed control.
The appliance, when installed must be
electrically connected and grounded in
accordance with local codes or, in the
absence of local codes, with the current
CSA C22.1 Canadian Electrical Code.
U.S. Installations, follow local codes and
the National Electrical Code, ANSI/NFPA
No. 70.
Should this fan require servicing, the
power supply must be disconnected. For
rewiring of any replacement components
refer to Figure 4.

Fan Removal Instructions

1. Turn off gas and electricity.
2. Remove the front glass.
3. Remove the logs.
CAUTION: Logs may be hot!
4. Remove burner assembly and rear log support plate.
5. Remove the fan mounting nuts (2 nuts). (Fig. 3)
6. Slip off the electrical connector at the motor.
7. Lift out the fan.
8. To reinstall reverse procedure.
Thermal Sensor is
Attached to Burner
Base
Screw Stud
Fan Speed Control/Junction Box
Fig. 3 Fan location.
Temperature Sensor
Speed
Control
Black
White
Ground
Fig. 4 Wiring diagram.
Screw
Stud
Fan is Installed at
the Back of the
Air Intake Box
FP1252
Fan
FP394
10000801