Sidewall Venting Graph - Vermont Castings D232 Installation Instructions & Homeowner's Manual

Free-standing direct vented fireplaces
Table of Contents

Advertisement

TO USE THE VENT GRAPH
1. Determine the height of the centre of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph (Fig. 12 ), locate
the point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line
to the bottom of the graph.
3. Select the indicated dimension, and position the fire-
place in accordance with same.
A:
EXAMPLE
If the vertical dimension from the floor of the fireplace is 11
feet (335cm) the horizontal run to the face of the outer wall
must not exceed 14 feet (427cm).
EXAMPLE B:
If the vertical dimension from the floor of the fireplace is 7
feet (214cm), the horizontal run to the face of the outer wall
must not exceed 8-1/2 feet (259cm).

SIDEWALL VENTING GRAPH

(Dimensions in Feet)
For D232
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
3
4
5 6 7
8 9 10 11 12 13 14 15 16 17 18 19 20
HORIZONTAL DIMENSION
SEE PAGE 13 & 14 FOR VENTING
REQUIREMENTS FOR SNORKELS.
eg: A
eg: B
SIDEWALL VENTING GRAPH
For FSDV42
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
3
4
5 6 7
REQUIREMENTS FOR SNORKELS.
Fig. 12
- 11 -
(Dimensions in Feet)
RFSDV42
ONLY
eg: A
eg: C
8 9 10 11 12 13 14 15 16 17 18 19 20
HORIZONTAL DIMENSION
SEE PAGE 14 FOR VENTING
Fig. 14b

Advertisement

Table of Contents
loading

Table of Contents