INSTALLER: Leave this manual with party responsible for use and operation.
OWNER: Retain this manual for future reference.
This fireplace uses SL300 Series Chimney
2" CLEARANCE TO COMBUSTIBLES AND BUILDING INSULATION FROM CHIMNEY REQUIRED.
NOTICE: DO NOT discard this manual!
Model(s):

WOODBURNING FIREPLACE

Installation and service of this fireplace should be
performed by qualified personnel. Vermont Cast-
ings Group recommends NFI certified profession-
als, or technicians supervised by an
NFI certified professional.
VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15
Installation Manual
Installation and Fireplace Setup
WARNING: If the information in these
instructions is not followed exactly, a fire
or explosion may result causing property
damage, personal injury, or death.
• DO NOT store or use gasoline or other flam-
mable vapors and liquids in the vicinity of this
or any other appliance.
• DO NOT overfire. Overfiring will void your
warranty.
• Comply with all minimum clearances to com-
bustibles as specified. Failure to comply may
cause house fire.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fireplace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other flammable
materials.
• Keep clothing, furniture, draperies and other flammable
materials away.
WARNING
Fire Risk.
For use with solid wood fuel only.
Other fuels may overfire and generate
poisonous gases (i.e. carbon monoxide).
1

Advertisement

Table of Contents
loading

Summary of Contents for Vermont Castings DSR36

  • Page 1: Woodburning Fireplace

    For use with solid wood fuel only. als, or technicians supervised by an NFI certified professional. Other fuels may overfire and generate poisonous gases (i.e. carbon monoxide). VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 2: Table Of Contents

    D. Secure Offset/Return E. Install Ceiling Firestops F. Install Attic Insulation Shield G. Roof Penetration H. Install Chase/Chase Top I. Termination Cap Requirements J. Install Termination Cap VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 3 Comments: Further description of the issues, who is responsible (Installer/Builder/Other Trades, etc.) and corrective action needed: Comments communicated to party responsible __________________________ by ______________________on _________ (Builder/Gen. Contractor) (Installer) (Date) 4012-132 • Rev A • 02/20/15 VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 4: Product Specific & Important Safety Information

    Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualified installer, service agency or your dealer. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 5: Getting Started

    4 ft. Decorative facing (1.322 m) off and trim ground level. Hearth extension Outside combustion air Factory-built fireplace Protective metal hearth strip(s) Figure 2.1 Typical Fireplace System VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 6: Design And Installation Considerations

    16 in. (406 mm) 1/2 in. (13 mm) all configurations 12 in. (305 mm) min. to perpendicular 48 in. wall. (1219 mm) Figure 2.2 Fireplace Locations VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 7: Locating Fireplace & Chimney

    • Below adjacent structure • Insulated exterior chase • Lower roof line in cooler climates • Avoid outside wall Windward Leeward Multi-level Roofs Figure 2.3 Recommended Chimney Locations VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 8: Tools And Supplies Needed

    Report to your dealer any parts damaged in shipment. • Read all the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 9: Framing And Clearances

    12 in. 9-5/8 in. (191 mm) (914 mm) (305 mm) (305 mm) (244 mm) 6 in. 7-1/8 in. (152 mm) (181 mm) Figure 3.1 Fireplace Dimensions VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 10: Clearances

    0 in. to level of standoffs 1/2 in. (13 mm) to sides of appliance 48 in. 1219 mm 0 in. to floor Figure 3.2 Clearances to Combustible Materials VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 11: Construct The Chase

    Figure 3.3. This will help reduce heat loss from the Figure 3.4 Chase Constructions home around the fireplace. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 12: Frame The Fireplace

    The fireplace should be positioned so the face of the non- combustible material on the fireplace will be flush with the face of the drywall on the walls. Level the fireplace and shim as necessary. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 13: Protective Metal Hearth Strips

    • DO NOT place outside air inlet hood close to exhaust vents or chimneys. Fumes or odor could be drawn into the room through the fireplace. • Locate outside air inlet hood to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause combustion air starvation. Figure 3.8 Outside Air Inlet Locations VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 14: Outside Air Installation

    Attach the door assembly to the fireplace using the screws provided. Flexible Duct (not supplied) Outside Air Plate Outside Air Assembly Hood 2 Wire Ties Figure 3.10 Outside Air Installation VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 15: Chimney And Termination Requirements

    16 ft (4.88 m) min. height (single offset-return) 47-1/4 in. 20 ft. (6.10 m) min. height (double offset-return) (1200 mm) 90 ft (27.4 m) max. height Effective Height Figure 4.1 Chimney Requirements VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 16: Offsets/Returns

    103 1/2 2629 49 1/4 1251 94 1/2 2400 Proper assembly of air-cooled chimney parts result in an overlap at chimney joints of 1-1/4 in. (32 mm). Effective length is built into this chart. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 17: Termination Requirements

    In a staggered installation with both gas and wood terminations, the wood termination cap must be higher than the gas termination cap. Figure 4.3 Multiple Chimney Locations VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 18: Chimney Installation

    Attic shield movement Ceiling firestops are required where chimney passes through ceiling or floor Figure 5.1 Typical Chimney System - Guidelines for Chimney System Installation VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 19: Assemble Chimney Sections

    Vertical straight runs of chimney must be supported every 35 ft (10.7 m). Figure 5.2 Assembling Chimney Sections WARNING! Risk of Fire! DO NOT install substitute or damaged chimney components. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 20: Secure Offset/Return

    • Use an attic insulation shield if the ceiling is insulated. The ceiling firestop may then be attached above or below the joists. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 21: Install Attic Insulation Shield

    If they have been connected correct- Ceiling Firestop Pipe (267 mm) ly, they will not disengage when tested. Figure 5.7 Install Attic Insulation Shield (firestop below ceiling) VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 22: Roof Penetration

    WARNING! Risk of Fire! DO NOT caulk the pipe to the chase top collar. • Caulk all seams to prevent leaks. .018 (26 ga) min. Galvanized Chase Top Figure 5.9 Chase Top Construction VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 23: Termination Cap Requirements

    Termination cap pipe and chimney section must be snapped together to maintain an overlap of 1-1/2 in. (38 mm). Figure 5.10 Installing a TR344 Round Termination Cap VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 24 Minimum Height Maximum Chase Top Chase Chimney Pipe Termination cap pipe and chimney section must overlap 1-1/2 in. (38 mm) Figure 5.15 Installing a DTO134/DTO146/DTS134/DTS146 Cap VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 25: Shrouds

    3 in (76 mm) air space from bottom of shroud Chase Top to top of chase. Figure 6.3 Shroud & TR Series cap with no Radiation Shield VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 26: Mailbox Style Shroud

    27 x 27 Min. Opening Width 686 x 686 Min. Height Above Bottom of Termination Cap Min. Opening Width Min. Opening Height Figure 6.5 Roofed Style Shroud Dimensions VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 27: Finishing

    2 in. (51 mm) Figure 7.2 Decorative Facing VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 28: Hearth Extension, Building And Finishing

    14.3-20.0 0.07-0.05 14 5/8 in. - 20 3/8 in. Marble • Choose finishing materials carefully. CAT. # 1321 Figure 7.3 Hearth Extension Dimensions VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 29: Fireplace Installed Flush On The Floor And Hearth Extension Raised To Bottom Of Firebox Opening

    Noncombustible HX4 or Framing Material equivalent Figure 7.4 Hearth Extension Construction Figure 7.6 Raised Platform Hearth Extension-Framing Non-combustible Finishing Materials Figure 7.7 Raised Platform Hearth Extension-Finishing VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 30: Raised Hearth Extension And Raised Fireplace

    Protective Metal Hearth Strips Non-combustible Floor and platform constructed of Framing Material wood or other combustible material Figure 7.8 Raised Hearth Extension and Fireplace Framing Materials VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 31: Non-Combustible Sealant Material

    Figure 7.9 Place Non-combustible Sealant WARNING! Risk of Fire! Vermont Castings Group is not responsible for discoloration, cracking or other material failures of finishing materials due to heat exposure or smoke. • Choose finishing materials carefully. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 32: Mantel And Wall Projections

    Steel, iron, 6 in./152 mm minimum brick, tile, concrete, slate, glass, plasters Seal joint with Measured from top of fireplace opening non-combustible sealant Figure 7.10 Mantel Specifications VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 33: Sidewalls/Surrounds

    40 in. [1016 mm] 12 in. 12 in. [305 mm] [305 mm] Figure 7.11 Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening) VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 34: Fireplace Setup

    National Fuel Gas Code Z223.1, Latest edition. WARNING! Do Not operate an unvented gas log set in this fireplace with the chimney removed. VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 35: Reference Materials

    Adapter - May be used with the following caps (527 mm) (203 mm) CT Series DT Series Outside 4-3/4 in. (121 mm) Diameter Effective Height 10-1/2 in. (267 mm) SL3 Chimney Stabilizer VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 36 JB877 Chimney Joint Band 24-5/8 in. 31 in. (625 mm) (787 mm) 10-1/2 in. (267 mm) RF371 Roof Flashing CB876 Chimney Joint Band 7 3/4 in. 26 in. CT-3A VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 37 15-5/8 in. (397 mm) ST375 Square Termination Cap 34-3/4 in. (883 mm) 32-1/2 in. (826 mm) TR-TVK - Top Vent Kit TR342 - Round Telescoping Termination Cap VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 38 22 3/4 in. 21 3/16 in. (577 mm) (538 mm) 46 in. 46 in. (1168 mm) (1168 mm) 26 in. 26 in. (660 mm) (660 mm) DTS146 DTO146 VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 39: Optional Components

    UD4 Uninsulated Duct LDSCPM - Corner Post Kit (for custom sizes) 4 in. (102 mm) i.d. 42 in. (1067 mm) LDS-BV Decorative Shroud Catalog # 12.5 15.5 LDS-BV VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...
  • Page 40 Vermont Castings Group 149 Cleveland Drive Paris, Kentucky 40361 www.vermontcastingsgroup.com VCG Designer Series • DSR36 Installation Manual • 4012-130 • Rev A • 02/20/15...

Table of Contents