Commissioning A New Unit / Ssd Download - Panasonic External Presentation unit 1728 Technical Description

Hide thumbs Also See for External Presentation unit 1728:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01297 Rev: 2
8
Technical Description External Presentation Unit 1728, ver. 1.4.x
Commissioning a new unit / SSD
download
The cable (RS485 line) to the ext. Presentation unit(s)
connected.
In the EBL512 c.i.e. the 1582 / 1587 board shall be mounted. Remove
the fuse "F1" on the 1582 / 1587 board.
The EBL128 c.i.e. shall be powerless and the "RS485 transceiver
component 4552" shall be plugged on the main board (4556).
On the EBL512 G3 main board (5010) remove the fuse "F19".
The SW mode and the address have to be set in each new unit
according to chapter "SW mode & Address setting", page 12. Here
follows a brief summary (a recommended sequence of actions):
1. Connect the cable from the c.i.e. to the ext. Presentation unit's
terminal block "J1".
2. When all connections are done put back the fuse "F1" on the
1582 / 1587 board in the EBL512 c.i.e. / power up the
EBL128 c.i.e. / put back the fuse "F19" on the main board
(5010) in the EBL512 G3 c.i.e., i.e. the ext. Presentation
unit(s) will now be powered up.
3. A brand new unit will automatically be ready for the SW mode
setting.
4. After SW mode and address setting press "P2" (yellow) and the
unit will restart, see chapter "Restart", page 19.
5. Since the SSD is not downloaded in the c.i.e. there will be a
fault message in the ext. Presentation unit's display:
"No contact with Control unit".
All LEDs in the ext. Presentation unit will be turned off.
6. Now the SSD have to be downloaded via Win512 / Win128 /
16
Win512 G3.
Win128 / Win512 G3 download SSD" dialog box, verify that
the "Download FBP / AAU" checkbox is marked. Start the
download of SSD.
15
One or more ext. Presentation units and/or ext. FBPs and/or Alert
Annunciation Units can be connected.
16
Via Win512 is the 1582 / 1587 board programmed (incl. its address). Via
Win512 / Win128 / Win512 G3 is each unit (e.g. an ext. Presentation unit)
programmed regarding the Address, Selective alarm presentation and if the
buzzer should be disabled.
messages" (alarm texts).
Connect the PC to the c.i.e. In the "Win512 /
When required, also "User definable text
17
15
shall be

Advertisement

Table of Contents
loading

Table of Contents