Commissioning of a new unit / SSD
download
The cable (RS485 line) to the AA unit(s)
diagram for the system respectively.
In the FT512 C.I.E. the 1587 board shall be mounted. Remove the fuse "F1"
on the 1587 board.
The FT128 C.I.E. Power shall be switched off and the "RS485 transceiver
component 4552" shall be plugged on the main board (4556).
On the FT1020G3 main board (5010) remove the fuse "F19".
The SW mode and the address have to be set in each new unit according to
chapter "SW mode & Address setting", page 13. Here follows a brief summary
(a recommended sequence of actions):
1.
Connect the cable from the C.I.E. to the AA unit's terminal block
"J1".
2.
When all connections are done put back the fuse "F1" on the 1587
board in the FT512 C.I.E. / power up the FT128 C.I.E. / put back
the fuse "F19" on the main board (5010) in the FT1020G3 C.I.E.,
i.e. the AA unit(s) will now be powered up.
3.
A brand new unit will automatically be ready for the SW mode
setting.
4.
After SW mode and address setting press "P2" (yellow) and the
unit will restart, see chapter "Restart", page 19.
5.
Since the SSD is not downloaded in the C.I.E. there will be a fault
message in the unit's display:
"No contact with Control unit"
All LED's in the unit will be turned off.
6.
Now the SSD have to be downloaded via Win512 / Win128 /
WinG3.
WinG3 download SSD" dialog box, verify that the "Download FBP /
AAU" checkbox is marked. Start the download of SSD.
7.
When the download of SSD to the C.I.E. is finished, it will restart.
Then the download of SSD to the AA unit(s) will take place. During
the download to an AA unit, the following will be shown in its
15
One or more external FBPs and/or Alert Annunciation Units can be connected.
16
Via Win512 is the 1587 board programmed. Via Win512 / Win128 / WinG3 is each
unit (e.g. an AA unit) programmed regarding Address, Selective alarm presentation, if
the buzzer should be disabled etc. When required, also "User definable text
messages" (alarm texts).
15
16
Connect the PC to the C.I.E. In the "Win512 / Win128 /
17
Technical Description
AAU 1736 – Rev 1